EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

PLC Systems: A Direct Integration Strategy for IEC 61850 MMS

Arthur Kniphoff da Cruz, Christian Siemers, Lorenz Däubler, Ana Clara Hackenhaar Kellermann, Jaine Mercia Fernandes de Oliveira

Automation · 08.06.2026 · 7 (3) · 85

DOI: 10.3390/automation7030085 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Automation, online erschienen am 08.06.2026. Verfasst von Arthur Kniphoff da Cruz und 4 weiteren Autor:innen. Die Arbeit nennt 29 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

This work proposes a vendor-independent integration method for International Electrotechnical Commission (IEC) 61850 Manufacturing Message Specification (MMS) communication protocol into Programmable Logic Controller (PLC) systems that support an open network communication interface available for the PLC program. IEC 61850 is globally well accepted for electrical substation control, and the protocol MMS is used for integrating the electrical substation bay level into the station level, where the PLC orchestrates the process level of the substation and parallel processes. This method was created because most PLCs lines do not natively support any protocol of IEC 61850, although it often needs to be used for the control of electrical substations. For the development of the prototype presented in this paper, PLCs from the Siemens AG families S7-1500 and S7-410, which support open communication over Transmission Control Protocol/Internet Protocol (TCP/IP) with external systems, were used for validation. Different results regarding network communication and PLC program performance are presented in this paper. The implemented solution presents a meaningful implementation of the MMS application layer into the PLC program and was successfully validated with real industrial, single and redundant PLC systems.

Zitieren

APA

Cruz, A. K. D., Siemers, C., Däubler, L., Kellermann, A. C. H., & Oliveira, J. M. F. D. (2026). PLC Systems: A Direct Integration Strategy for IEC 61850 MMS. Automation, 7(3), 85. https://doi.org/10.3390/automation7030085

Vancouver

Cruz AKD, Siemers C, Däubler L, Kellermann ACH, Oliveira JMFD. PLC Systems: A Direct Integration Strategy for IEC 61850 MMS. Automation. 2026;7(3):85. doi:10.3390/automation7030085

BibTeX
@article{Cruz2026,
  author = {Cruz, Arthur Kniphoff da and Siemers, Christian and Däubler, Lorenz and Kellermann, Ana Clara Hackenhaar and Oliveira, Jaine Mercia Fernandes de},
  title = {PLC Systems: A Direct Integration Strategy for IEC 61850 MMS},
  journal = {Automation},
  year = {2026},
  volume = {7},
  number = {3},
  pages = {85},
  doi = {10.3390/automation7030085}
}
Kostenlos starten →