EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

Integrated Network Reconfiguration and Adaptive Protection Coordination in Active Distribution Systems

Husham Sajir, Ersagun Kürşat Yaylacı

Applied Sciences · 18.11.2026 · 16 (22) · 11423

DOI: 10.3390/app162211423 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Applied Sciences, online erschienen am 18.11.2026. Verfasst von Husham Sajir und 1 weiteren Autor:innen. Die Arbeit nennt 44 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

The widespread use of distributed generation (DG) and renewable energy resources (RES) in contemporary distribution networks significantly alters optimal topology configurations, protection coordination requirements, and network operating conditions. This paper presents a thorough two-stage optimization framework for the concurrent optimization of adaptive protection coordination and distribution network reconfiguration (DNR) in renewable-integrated active distribution systems. The framework addresses the dual issues of ensuring reliable relay coordination under dynamically fluctuating fault current levels caused by variable DG output and minimizing active power losses through optimal switch reconfiguration. The Harmony Search Algorithm (HSA) is used in Stage I minimize active power losses at four loading levels (100–220% of nominal demand), subject to radiality, voltage and branch-current constraints, thereby determining the ideal radial network topology. To satisfy all Coordination Time Interval (CTI) constraints, Stage II uses a hybrid Genetic Algorithm–Sequential Quadratic Programming (GA–SQP) approach that combines the precise local refinement of SQP with the global exploration of GA to determine the optimal Time Dial Settings (TDS) of directional overcurrent relays for the reconfigured network. For any resulting radial topology, an automated graph analysis algorithm dynamically finds primary–backup relay pairs, eliminating the need for human operator intervention in the protection coordination loop. Relay settings are determined for each loading level using the DG fault-current contributions obtained from a positive-sequence short-circuit analysis of a balanced three-phase fault at the midpoint of each line. Network reconfiguration lowers the active power loss by 21.42%, 28.24%, 31.70%, and 33.88%, respectively, while maintaining the minimum voltage above 0.90 pu, according to simulations of the DG-integrated IEEE 33-bus system at four loading levels (100–220% of nominal demand); the same configurations are obtained in repeated HSA runs with different random seeds. The DG units must be included in the reconfiguration problem, since an optimal configuration without them increases the loss by 33.9% when they are added. Relay coordination is linear in the TDS variables for fixed pickup currents; it is solved by the hybrid GA–SQP and validated against the exact linear-programming optimum: the total primary operating time of the 32 relays is 18.14–19.47 s (0.57–0.61 s per relay; maximum 1.36 s), and all 31 primary–backup pairings satisfy a CTI of 0.2 s. This per-relay time is less than the figures published for standalone GA (3.71 s) and HHO-SQP (1.33 s) coordination at nominal loads. The primary contribution of this work is the integration of protection coordination and reconfiguration into a single framework.

Zitieren

APA

Sajir, H., & Yaylacı, E. K. (2026). Integrated Network Reconfiguration and Adaptive Protection Coordination in Active Distribution Systems. Applied Sciences, 16(22), 11423. https://doi.org/10.3390/app162211423

Vancouver

Sajir H, Yaylacı EK. Integrated Network Reconfiguration and Adaptive Protection Coordination in Active Distribution Systems. Applied Sciences. 2026;16(22):11423. doi:10.3390/app162211423

BibTeX
@article{Sajir2026,
  author = {Sajir, Husham and Yaylacı, Ersagun Kürşat},
  title = {Integrated Network Reconfiguration and Adaptive Protection Coordination in Active Distribution Systems},
  journal = {Applied Sciences},
  year = {2026},
  volume = {16},
  number = {22},
  pages = {11423},
  doi = {10.3390/app162211423}
}
Kostenlos starten →