EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

Seismic Fragility of Representative High-Voltage Electrical Equipment Considering Joint Ground-Motion and Material Variability

Liang Cheng, Jinqiang Peng, Yanhui Liu, Yindong Gong, Hao Li, Wanchen Meng

Applied Sciences · 28.10.2026 · 16 (21) · 10680

DOI: 10.3390/app162110680 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Applied Sciences, online erschienen am 28.10.2026. Verfasst von Liang Cheng und 5 weiteren Autor:innen. Die Arbeit nennt 43 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: National Natural Science Foundation of China.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Ground-motion variability and uncertain material properties affect seismic tensile demand in high-voltage equipment. This study examines idealized 550 kV circuit-breaker, current-transformer, and voltage-transformer configurations using finite-element models, joint parameter–record sampling, and elastic first-passage fragility analysis. Bidirectional linear modal responses are combined with fixed gravity stresses; the intensity measure is the geometric mean of horizontal component PGAs. Record metadata, response spectra, available numerical verification, and clustered statistical uncertainty are reported. For the circuit breaker, the lower porcelain post governs all 60 combinations; the fixed-strength fragility median and logarithmic dispersion are 0.528 g and 0.441. For the current transformer, incorporating sampled tensile strength gives a demand-model median of 0.859 g and dispersion of 0.320. For the voltage transformer, direct first-passage capacity medians are 0.144 g, 0.469 g, and 1.551 g from the lower to upper insulating section. Between-record differences account for 99.4% and 99.7% of the observed log-capacity sums of squares in the two transformer ensembles under the adopted 2% material variability. These are conditional elastic tensile-threshold estimates, with uncalibrated material statistics and incomplete device-specific experimental validation; they do not establish a general ranking of equipment types or predict electrical functionality.

Förderung

  • National Natural Science Foundation of China

Zitieren

APA

Cheng, L., Peng, J., Liu, Y., Gong, Y., Li, H., & Meng, W. (2026). Seismic Fragility of Representative High-Voltage Electrical Equipment Considering Joint Ground-Motion and Material Variability. Applied Sciences, 16(21), 10680. https://doi.org/10.3390/app162110680

Vancouver

Cheng L, Peng J, Liu Y, Gong Y, Li H, Meng W. Seismic Fragility of Representative High-Voltage Electrical Equipment Considering Joint Ground-Motion and Material Variability. Applied Sciences. 2026;16(21):10680. doi:10.3390/app162110680

BibTeX
@article{Cheng2026,
  author = {Cheng, Liang and Peng, Jinqiang and Liu, Yanhui and Gong, Yindong and Li, Hao and Meng, Wanchen},
  title = {Seismic Fragility of Representative High-Voltage Electrical Equipment Considering Joint Ground-Motion and Material Variability},
  journal = {Applied Sciences},
  year = {2026},
  volume = {16},
  number = {21},
  pages = {10680},
  doi = {10.3390/app162110680}
}
Kostenlos starten →