EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

Research on Safety Distance Calculation and Altitude Correction Methods for On-Site Withstand Voltage Tests of UHV AC Equipment

Wenlong Liao, Yueping Yang, Xiaoxu Ma, Yu Tian, Yujian Ding

Applied Sciences · 02.06.2026 · 16 (11) · 5547

DOI: 10.3390/app16115547 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Applied Sciences, online erschienen am 02.06.2026. Verfasst von Wenlong Liao und 4 weiteren Autor:innen. Die Arbeit nennt 27 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: State Grid Sichuan Electric Power Company Scientific and Technological Project.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

On-site withstand voltage testing is essential for evaluating insulation performance and detecting defects in UHV AC equipment; however, existing safety distance criteria are mainly based on empirical experience or extrapolated from low-altitude and lower-voltage conditions, limiting their applicability. To address this issue, a systematic framework for safety distance calculation and altitude correction is developed. The selection principles and circuit configuration of the test system are analyzed to clarify the constraints between power capacity and tuning under high-voltage, large-capacity conditions. Based on air-gap discharge characteristics, a minimum safety distance model is established for the 1000 kV main transformer with respect to grounded structures and personnel. Meteorological factors and proximity effects are further incorporated to propose correction methods and on-site zoning strategies. Results indicate that a baseline safety distance of approximately 10 m is appropriate at altitudes up to 1000 m, and the model captures the nonlinear degradation of insulation strength in long air gaps at higher altitudes. A case study at 3620 m yields a minimum safety distance of 16.4 m, providing a quantitative basis for safe UHV AC on-site testing under varying altitude conditions.

Förderung

  • State Grid Sichuan Electric Power Company Scientific and Technological Project

Zitieren

APA

Liao, W., Yang, Y., Ma, X., Tian, Y., & Ding, Y. (2026). Research on Safety Distance Calculation and Altitude Correction Methods for On-Site Withstand Voltage Tests of UHV AC Equipment. Applied Sciences, 16(11), 5547. https://doi.org/10.3390/app16115547

Vancouver

Liao W, Yang Y, Ma X, Tian Y, Ding Y. Research on Safety Distance Calculation and Altitude Correction Methods for On-Site Withstand Voltage Tests of UHV AC Equipment. Applied Sciences. 2026;16(11):5547. doi:10.3390/app16115547

BibTeX
@article{Liao2026,
  author = {Liao, Wenlong and Yang, Yueping and Ma, Xiaoxu and Tian, Yu and Ding, Yujian},
  title = {Research on Safety Distance Calculation and Altitude Correction Methods for On-Site Withstand Voltage Tests of UHV AC Equipment},
  journal = {Applied Sciences},
  year = {2026},
  volume = {16},
  number = {11},
  pages = {5547},
  doi = {10.3390/app16115547}
}
Kostenlos starten →