EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

Optimal Coordination of Distance and Two-Level Directional Overcurrent Relays for Renewable Energy-Integrated Power Networks Using Enhanced Red-Tailed Hawk Algorithm

Birsen Boylu Ayvaz, Zafer Dogan

Applied Sciences · 19.04.2026 · 16 (8) · 3961

DOI: 10.3390/app16083961 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Applied Sciences, online erschienen am 19.04.2026. Verfasst von Birsen Boylu Ayvaz und 1 weiteren Autor:innen. Die Arbeit nennt 48 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Optimal coordination of distance and directional overcurrent relays (DR–DOCR) aims to achieve a fast, selective, and reliable protection scheme for transmission and sub-transmission systems. However, it constitutes a complex, nonlinear, and highly constrained optimization problem. In particular, single-setting DOCR characteristics used in conventional DR-DOCR coordination introduce additional challenges in lowering relay operating times while satisfying the coordination time interval (CTI) constraint. To address this issue, this paper proposes a novel DR-DOCR coordination approach that leverages a two-level DOCR characteristic. The objective is to exploit this characteristic, which partitions the relay curve into primary and backup protection regions in a highly flexible manner, thereby enabling easier avoidance of CTI violations. In addition, an enhanced variant of the red-tailed hawk algorithm, called ERTH, has been newly developed to solve this challenging problem. The proposed method is validated on versions of the 8-bus and 33-kV portion of the 30-bus power networks that have been modified to include renewable energy sources. Results demonstrate that the proposed method achieves total relay operating times of 23.681 s and 70.742 s for the 8-bus and 30-bus power systems, respectively. These values correspond to an 80.4% and 81.2% reduction compared to the conventional coordination scheme optimized by the ERTH algorithm, which yields 120.702 s and 376.757 s, respectively. Moreover, the ERTH algorithm exhibits superior performance in attaining near-global optimal solutions compared to the original RTH and other competitive optimization algorithms. In particular, for the 30-bus system under the conventional coordination scheme, the second-best result after ERTH is obtained by the teaching-learning-based optimization algorithm with a total relay operating time of 415.885 s. This indicates a 9.4% improvement achieved by ERTH (376.757 s) and a significantly higher improvement of 83% (70.742 s) achieved by the proposed strategy integrating ERTH with the two-level DOCR-based coordination scheme.

Zitieren

APA

Ayvaz, B. B., & Dogan, Z. (2026). Optimal Coordination of Distance and Two-Level Directional Overcurrent Relays for Renewable Energy-Integrated Power Networks Using Enhanced Red-Tailed Hawk Algorithm. Applied Sciences, 16(8), 3961. https://doi.org/10.3390/app16083961

Vancouver

Ayvaz BB, Dogan Z. Optimal Coordination of Distance and Two-Level Directional Overcurrent Relays for Renewable Energy-Integrated Power Networks Using Enhanced Red-Tailed Hawk Algorithm. Applied Sciences. 2026;16(8):3961. doi:10.3390/app16083961

BibTeX
@article{Ayvaz2026,
  author = {Ayvaz, Birsen Boylu and Dogan, Zafer},
  title = {Optimal Coordination of Distance and Two-Level Directional Overcurrent Relays for Renewable Energy-Integrated Power Networks Using Enhanced Red-Tailed Hawk Algorithm},
  journal = {Applied Sciences},
  year = {2026},
  volume = {16},
  number = {8},
  pages = {3961},
  doi = {10.3390/app16083961}
}
Kostenlos starten →