Response of Transmission Tower Guy Wires Under Impact: Theoretical Analysis and Finite Element Simulation
Applied Sciences · 22.12.2025 · 16 (1) · 123
DOI: 10.3390/app16010123 ↗Kurz gefasst
Fachartikel in der Zeitschrift Applied Sciences, online erschienen am 22.12.2025. Verfasst von Jin-Gang Yang und 6 weiteren Autor:innen. Die Arbeit wurde bisher 1-mal zitiert (Crossref) und nennt 19 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Science and Technology Project of State Grid Power Space Technology Co., Ltd..
Abstract (Originalsprache)
Transmission tower guy wires are critical flexible tension members ensuring the stability and safe operation of overhead power transmission networks. However, these components are vulnerable to external impacts from falling rocks, ice masses, and other natural hazards, which can cause excessive deformation, anchorage loosening, and catastrophic failure. Current design standards primarily consider static loads, lacking comprehensive models for predicting dynamic impact responses. This study presents a theoretical model for predicting the peak impact response of guy wires by modeling the impact process as a point mass impacting a nonlinear spring system. Using an energy-based elastic potential method combined with cable theory, analytical solutions for axial force, displacement, and peak impact force are derived. Newton–Cotes numerical integration solves the implicit function to obtain closed-form solutions for efficient prediction. Validated through finite element simulations, deviations of peak displacement, peak impact force, and peak axial force between theoretical and numerical results are within ±4%, ±18%, and ±4%, respectively. Using the validated model, parametric studies show that increasing the inclination angle from 15° to 55° slightly reduces peak displacement by 2–4%, impact force by 1–13%, and axial force by 1–10%. Higher prestress (100–300 MPa) decreases displacement and impact force but increases axial force. Longer lengths (15–55 m) cause linear displacement growth and nonlinear force reduction. Impacts near anchorage points help control displacement risks, and impact velocity generally has a more significant influence on response characteristics than impactor mass. This model provides a scientific basis for impact-resistant design of power grid infrastructure and guidance for optimizing de-icing strategies, enhancing transmission system safety and reliability.
Förderung
- Science and Technology Project of State Grid Power Space Technology Co., Ltd.
Zitieren
APA
Yang, J., Li, S., Zhou, C., Li, L., Tian, B., Yang, W., & Zhang, S. (2025). Response of Transmission Tower Guy Wires Under Impact: Theoretical Analysis and Finite Element Simulation. Applied Sciences, 16(1), 123. https://doi.org/10.3390/app16010123
Vancouver
Yang J, Li S, Zhou C, Li L, Tian B, Yang W, et al. Response of Transmission Tower Guy Wires Under Impact: Theoretical Analysis and Finite Element Simulation. Applied Sciences. 2025;16(1):123. doi:10.3390/app16010123
BibTeX
@article{Yang2025,
author = {Yang, Jin-Gang and Li, Shuai and Zhou, Chen-Guang and Li, Liu-Yi and Tian, Bang and Yang, Wen-Gang and Zhang, Shi-Hui},
title = {Response of Transmission Tower Guy Wires Under Impact: Theoretical Analysis and Finite Element Simulation},
journal = {Applied Sciences},
year = {2025},
volume = {16},
number = {1},
pages = {123},
doi = {10.3390/app16010123}
}