An Operation State Detection Method of DC Grounding Electrodes Based on Surface Potential Distribution

Yuan Jiang, Jing Zhou, Zhanlong Zhang, Yihua Dan, Hao Wu

Applied Sciences · 25.02.2025 · 15 (5) · 2461

DOI: 10.3390/app15052461 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Applied Sciences, online erschienen am 25.02.2025. Verfasst von Yuan Jiang und 4 weiteren Autor:innen. Die Arbeit wurde bisher 1-mal zitiert (Crossref) und nennt 35 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

During the long-term operation of the DC grounding electrode of the converter station, there are often hazards such as heating and aging of the coke layer, and burning and corrosion at the connection between the feed rod and the cable, resulting in break problems at the connection between the cable and the feed rod. Currently, the operational status monitoring of grounding electrodes primarily relies on daily tracking of well temperature, humidity, and water level characteristics; periodic testing; and on-site excavation. However, the above methods cannot accurately obtain the breakage location information at the connection between the cable and the feed rod. To address these issues, this paper first analyzes the current distribution law in the feeder rod of the DC grounding electrode. Subsequently, it studies the impact of localized fractures in the DC grounding electrode on the surface potential distribution characteristics. Finally, an Operation State Detection Method (OSDM) based on potential distribution is proposed and validated through case studies, demonstrating high measurement accuracy. The results indicate that OSDM can effectively monitor the operational status of DC grounding electrodes, providing a reference for their maintenance and repair.

Zitieren

APA

Jiang, Y., Zhou, J., Zhang, Z., Dan, Y., & Wu, H. (2025). An Operation State Detection Method of DC Grounding Electrodes Based on Surface Potential Distribution. Applied Sciences, 15(5), 2461. https://doi.org/10.3390/app15052461

Vancouver

Jiang Y, Zhou J, Zhang Z, Dan Y, Wu H. An Operation State Detection Method of DC Grounding Electrodes Based on Surface Potential Distribution. Applied Sciences. 2025;15(5):2461. doi:10.3390/app15052461

BibTeX
@article{Jiang2025,
  author = {Jiang, Yuan and Zhou, Jing and Zhang, Zhanlong and Dan, Yihua and Wu, Hao},
  title = {An Operation State Detection Method of DC Grounding Electrodes Based on Surface Potential Distribution},
  journal = {Applied Sciences},
  year = {2025},
  volume = {15},
  number = {5},
  pages = {2461},
  doi = {10.3390/app15052461}
}
Kostenlos starten →