EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

Energy and Environmental Performance Comparison of Heat Pump Systems Working with Alternative Refrigerants

Matteo Dongellini, Christian Natale, Claudia Naldi, Eugenia Rossi di Schio, Paolo Valdiserri, Gian Luca Morini

Applied Sciences · 17.06.2023 · 13 (12) · 7238

DOI: 10.3390/app13127238 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Applied Sciences, online erschienen am 17.06.2023. Verfasst von Matteo Dongellini und 5 weiteren Autor:innen. Die Arbeit wurde bisher 19-mal zitiert (Crossref) und nennt 36 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Italian Ministry of University and Research (MUR) within the framework of the PRIN2017 project «The energy FLEXibility of enhanced HEAT pumps for the next gene…, PNRR—Missione 4—Componente 2, Investimento 1.5 Creazione e rafforzamento di Ecosistemi dell’innovazione, costruzione di leader territoriali di R&S D.D, research project ECOSISTER-Ecosystem for Sustainable Transition in Emilia-Romagna (Spoke N. 4—Smart mobility, housing and energy solutions for a carbon-neutral….

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

The European Parliament has imposed to reduce by 2030 whole HFC emissions by at least two-thirds with respect to 2014 levels. With the aim of contributing to determine the energy and environmental advantages of refrigerants alternative to R-410A, this paper reports the results of a numerical study focused on an HVAC system coupled to a residential building and based on a reversible electric heat pump. In particular, two heat pump typologies are considered: an air-source and a ground-source heat pump, both operating with the two refrigerants R-410A and R-454B. The environmental performance of the studied system is assessed by means of the TEWI (total equivalent warming impact) index. The adoption of R-454B involves a slight decrease (2–3%) in the overall annual energy performance of the system with respect to the use of R-410A. On the other hand, the working fluid R-454B guarantees a marked decrease in the TEWI indicator. Indeed, considering the current Italian emission factor of electricity taken from the grid, the total emissions over the entire heat pump operating life drop by about 25% and can decrease by up to 89% in perspective, following the current reduction trend of the emission factor.

Förderung

  • Italian Ministry of University and Research (MUR) within the framework of the PRIN2017 project «The energy FLEXibility of enhanced HEAT pumps for the next gene…
  • PNRR—Missione 4—Componente 2, Investimento 1.5 Creazione e rafforzamento di Ecosistemi dell’innovazione, costruzione di leader territoriali di R&S D.D
  • research project ECOSISTER-Ecosystem for Sustainable Transition in Emilia-Romagna (Spoke N. 4—Smart mobility, housing and energy solutions for a carbon-neutral…

Zitieren

APA

Dongellini, M., Natale, C., Naldi, C., Schio, E. R. D., Valdiserri, P., & Morini, G. L. (2023). Energy and Environmental Performance Comparison of Heat Pump Systems Working with Alternative Refrigerants. Applied Sciences, 13(12), 7238. https://doi.org/10.3390/app13127238

Vancouver

Dongellini M, Natale C, Naldi C, Schio ERD, Valdiserri P, Morini GL. Energy and Environmental Performance Comparison of Heat Pump Systems Working with Alternative Refrigerants. Applied Sciences. 2023;13(12):7238. doi:10.3390/app13127238

BibTeX
@article{Dongellini2023,
  author = {Dongellini, Matteo and Natale, Christian and Naldi, Claudia and Schio, Eugenia Rossi di and Valdiserri, Paolo and Morini, Gian Luca},
  title = {Energy and Environmental Performance Comparison of Heat Pump Systems Working with Alternative Refrigerants},
  journal = {Applied Sciences},
  year = {2023},
  volume = {13},
  number = {12},
  pages = {7238},
  doi = {10.3390/app13127238}
}
Kostenlos starten →