Abstract (Originalsprache)

Buildings account for a significant portion of global electricity consumption, highlighting the need for cost-effective energy management strategies. This paper presents a measurement-driven energy management and decision-support framework integrating demand response (DR) and battery energy storage systems (BESSs) for campus buildings. Using measured electricity demand and rooftop photovoltaic generation data from the Engineering Laboratory Building (ELB) at the University of Michigan–Dearborn, a mixed-integer linear programming (MILP) model evaluates four operating scenarios under a utility tariff-based cost structure. A graphical user interface (GUI) is also developed to facilitate practical application of the framework and support campus operators in evaluating energy management and system upgrade alternatives. Results for May 2026 demonstrate electricity cost reductions of 19.6% with DR alone and 32.5% with coordinated DR–BESS operation, while the corresponding savings over six months are 14.3% and 26.9%. However, the estimated battery payback period of 14.5–16.6 years highlights the importance of economic feasibility in investment decisions. The findings provide actionable recommendations for campus operators, prioritizing DR implementation and identifying BESSs as a potential subsequent upgrade based on economic benefits and building load characteristics.

Zitieren

APA

Beidoun, A., Hoang, Q. M., Hollweg, G. V., & Bui, V. (2026). Optimal Demand Response-Based Energy Management for Campus Buildings with Battery Energy Storage Systems: A Case Study of the ELB Building. Algorithms, 19(12), 1021. https://doi.org/10.3390/a19121021

Vancouver

Beidoun A, Hoang QM, Hollweg GV, Bui V. Optimal Demand Response-Based Energy Management for Campus Buildings with Battery Energy Storage Systems: A Case Study of the ELB Building. Algorithms. 2026;19(12):1021. doi:10.3390/a19121021

BibTeX
@article{Beidoun2026,
  author = {Beidoun, Ali and Hoang, Quang Manh and Hollweg, Guilherme Vieira and Bui, Van-Hai},
  title = {Optimal Demand Response-Based Energy Management for Campus Buildings with Battery Energy Storage Systems: A Case Study of the ELB Building},
  journal = {Algorithms},
  year = {2026},
  volume = {19},
  number = {12},
  pages = {1021},
  doi = {10.3390/a19121021}
}