Salwa F. R. Tuasikal, Marceau Haurissa, Arnold J. Kastanja

Jurnal JEETech · 11.11.2026 · 7 (2) · 306-316

DOI: 10.32492/jeetech.v7i2.7211 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Jurnal JEETech, online erschienen am 11.11.2026. Verfasst von Salwa F. R. Tuasikal und 2 weiteren Autor:innen. Der Volltext ist frei zugänglich (Open Access, CC BY-NC 4.0).

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

This study assessed the voltage profile of the cascaded Karpan 1-Kuda-OSM 20 kV network in Ambon and evaluated transformer tap adjustment as a corrective action. Primary data from PT PLN (Persero) UP3 Ambon included single-line diagrams, conductor parameters, transformer ratings, feeder lengths, installed loads, and measured peak loads. The network was modelled in ETAP and solved by the Newton-Raphson load-flow method under installed-load and peak-load scenarios. Manual three-phase voltage-drop calculations were used to check the OSM segment. Before correction, the terminal voltage at LBS Wainitu was 19.12 kV under installed load and 19.32 kV under peak load. Across the 31.061 km cascaded path, the voltage drops were 0.51 kV (2.6%) and 0.34 kV (1.7%), respectively. Although both met the 5% radial-feeder criterion, the installed-load terminal voltage was only 0.12 kV above the 0.95 pu reference. A -2.5% primary fixed-tap adjustment on transformers T1 and T3 raised the sending voltage to 20.15 kV and 20.18 kV. Consequently, the terminal voltage increased by 0.53 kV to 19.65 kV and 19.85 kV. The correction improved voltage margin without materially changing the line-drop percentage, indicating that the dominant voltage deficit originated at the sending bus rather than in the OSM segment.

Zitieren

APA

Tuasikal, S. F. R., Haurissa, M., & Kastanja, A. J. (2026). ETAP-Based Voltage Profile Assessment and Tap-Changer Improvement of the 20 kV OSM Feeder. Jurnal JEETech, 7(2), 306-316. https://doi.org/10.32492/jeetech.v7i2.7211

Vancouver

Tuasikal SFR, Haurissa M, Kastanja AJ. ETAP-Based Voltage Profile Assessment and Tap-Changer Improvement of the 20 kV OSM Feeder. Jurnal JEETech. 2026;7(2):306-316. doi:10.32492/jeetech.v7i2.7211

BibTeX
@article{Tuasikal2026,
  author = {Tuasikal, Salwa F. R. and Haurissa, Marceau and Kastanja, Arnold J.},
  title = {ETAP-Based Voltage Profile Assessment and Tap-Changer Improvement of the 20 kV OSM Feeder},
  journal = {Jurnal JEETech},
  year = {2026},
  volume = {7},
  number = {2},
  pages = {306--316},
  doi = {10.32492/jeetech.v7i2.7211}
}
Kostenlos starten →