Closed-Loop Performance Analysis and PID Control of an Evaporative-Desiccant Cooler Using Palm-Stem Fibre and Alhagi Graecorum Pads with Silica-Gel Adsorption
International Journal of Robotics and Control Systems · 17.06.2026 · 6 (4) · 3468-3486
DOI: 10.31763/ijrcs.v6i4.2644 ↗Kurz gefasst
Fachartikel in der Zeitschrift International Journal of Robotics and Control Systems, online erschienen am 17.06.2026. Verfasst von Abadal-Salam T. Hussain und 9 weiteren Autor:innen. Der Volltext ist frei zugänglich (Open Access, CC BY-SA 4.0).
Abstract (Originalsprache)
The hot-dry climate of central and southern Iraq imposes high summer cooling demand that conventional vapour-compression air-conditioners satisfy only at substantial electricity cost, motivating low-power evaporative-cooling alternatives. However, evaporative coolers operating in unconditioned environments exhibit non-linear coupling between airflow, pad wetting, and downstream desiccant adsorption that is not addressed by existing on/off control schemes, leaving no validated controller-tuning guidance for integration into building management systems (BMS). The research contribution is threefold: (i) experimental characterisation of a hybrid evaporative-desiccant cooler with two locally available organic pads - palm-stem fibre (PSF) and alhagi graecorum (AGP) - coupled with a silica-gel adsorption stage; (ii) identification of a first-order-plus-deadtime (FOPDT) plant model from step-response data for closed-loop synthesis; and (iii) design, tuning, and stability analysis of a PID controller enabling outlet-temperature regulation against ambient disturbances. A locally fabricated 12 V DC test rig was instrumented for outlet temperature, relative humidity, pressure drop, and water consumption at three Reynolds numbers (4.2 × 10?, 5.6 × 10?, 7.7 × 10?), with five replicates per condition and uncertainty propagation per ASME PTC 19.1. The AGP-silica-gel configuration achieved a saturation efficiency of 94.6 ± 1.2 % (95 % CI), a 12.4 % improvement over a commercial CELdek 7090 baseline; supply-air RH dropped from 64.9 % (PSF) to 54.4 % (AGP + desiccant); water consumption fell to 1.5 L h?¹. The closed-loop PID system achieved a settling time of 78 s with gain margin 8.6 dB and phase margin 62°, demonstrating robust BMS-compatible regulation across ±20 % plant-parameter perturbation.
Zitieren
APA
Hussain, A. T., Hamad, Z. K., Almulaisi, T., Saleh, Z. H., Ahmed, A. H., Fadhil, H. A., Ismaeel, M. M., Al-Bahran, H. A., Ahmed, O. K., & Merie, F. H. (2026). Closed-Loop Performance Analysis and PID Control of an Evaporative-Desiccant Cooler Using Palm-Stem Fibre and Alhagi Graecorum Pads with Silica-Gel Adsorption. International Journal of Robotics and Control Systems, 6(4), 3468-3486. https://doi.org/10.31763/ijrcs.v6i4.2644
Vancouver
Hussain AT, Hamad ZK, Almulaisi T, Saleh ZH, Ahmed AH, Fadhil HA, et al. Closed-Loop Performance Analysis and PID Control of an Evaporative-Desiccant Cooler Using Palm-Stem Fibre and Alhagi Graecorum Pads with Silica-Gel Adsorption. International Journal of Robotics and Control Systems. 2026;6(4):3468-3486. doi:10.31763/ijrcs.v6i4.2644
BibTeX
@article{Hussain2026,
author = {Hussain, Abadal-Salam T. and Hamad, Zeyad Khalaf and Almulaisi, Taha and Saleh, Ziyaad H. and Ahmed, Ahmed H. and Fadhil, Hilal A. and Ismaeel, Marwa M. and Al-Bahran, Hussein Ali and Ahmed, Omer K. and Merie, Firas Hussein},
title = {Closed-Loop Performance Analysis and PID Control of an Evaporative-Desiccant Cooler Using Palm-Stem Fibre and Alhagi Graecorum Pads with Silica-Gel Adsorption},
journal = {International Journal of Robotics and Control Systems},
year = {2026},
volume = {6},
number = {4},
pages = {3468--3486},
doi = {10.31763/ijrcs.v6i4.2644}
}
EUVIMED