Modular AC Condenser Waste-Heat Recovery for Service-Water Preheating
The Sydney Journal of Interdisciplinary Engineering · 18.11.2026 · 2 (1) · 54-57
DOI: 10.30722/jqmtev85 ↗Kurz gefasst
Fachartikel in der Zeitschrift The Sydney Journal of Interdisciplinary Engineering, online erschienen am 18.11.2026.
Abstract (Originalsprache)
Thermal imaging identified an outdoor AC condenser as a low-grade waste heat source, with a measured local temperature difference of approximately 26 °C. A removable finned-tube HX was designed to recover condenser exhaust heat for service-water preheating without modifying the refrigerant circuit. Under moderate assumptions, the proposed system recovered 2.61 kW, equivalent to 15.77 kWh day⁻¹ and a theoretical electricity offset of approximately $5.17 day⁻¹ per condenser. The design is most suitable for sites where cooling operation overlaps with nearby hot-water demand.
Zitieren
APA
(2026). Modular AC Condenser Waste-Heat Recovery for Service-Water Preheating. The Sydney Journal of Interdisciplinary Engineering, 2(1), 54-57. https://doi.org/10.30722/jqmtev85
Vancouver
Modular AC Condenser Waste-Heat Recovery for Service-Water Preheating. The Sydney Journal of Interdisciplinary Engineering. 2026;2(1):54-57. doi:10.30722/jqmtev85
BibTeX
@article{euvimed2026,
title = {Modular AC Condenser Waste-Heat Recovery for Service-Water Preheating},
journal = {The Sydney Journal of Interdisciplinary Engineering},
year = {2026},
volume = {2},
number = {1},
pages = {54--57},
doi = {10.30722/jqmtev85}
}