EUVIMEDEUVIMED entdecken
Crossref

Analysis and Suppression of Sending-End Transient Overvoltage in A Wind Power Integrated LCC-HVDC System under Commutation Failure

He Wang, Han Zhang, Jiajun Ma, Jing Bian, Jiazhi Guo

Power and Energy Future · 2026

DOI: 10.26599/pef.2026.9650018 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Power and Energy Future, 2026. Verfasst von He Wang und 4 weiteren Autor:innen. Die Arbeit nennt 18 Literaturangaben.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Receiving-end AC faults in line-commutated-converter-based high-voltage direct-current (LCC-HVDC) systems may trigger commutation failures (CFs) and cause sending-end transient overvoltage (TOV) during recovery. Existing work emphasizes rectifier reactive power control and DC current recovery, but the DC current undershoot from constant current controller over-regulation and its effect on sending-end TOV are not well studied. This paper analyzes the coupling among DC current, rectifier reactive consumption, AC filter reactive output, wind farm reactive response, and sending-end bus voltage during CFs. It reveals that the current undershoot reduces rectifier reactive consumption, aggravating the sending-end reactive surplus and elevating the peak TOV. A TOV assessment method incorporating the dynamic reactive response of wind farms is developed, along with a voltage-threshold-constrained DC current undershoot suppression strategy (VTC-DUS). The VTC-DUS calculates a current lower limit from a preset voltage threshold to form a modified DC current order, and adjusts the voltage-dependent current order limiter characteristic by the deviation between the modified and actual currents to suppress the excessive current drop. PSCAD/EMTDC simulations indicate that the peak TOV errors of the proposed method are below 0.01 pu for three-phase-to-ground faults and 0.03 pu for single-phase-to-ground faults, and that VTC-DUS effectively reduces the sending-end peak TOV under various fault conditions.

Zitieren

APA

Wang, H., Zhang, H., Ma, J., Bian, J., & Guo, J. (2026). Analysis and Suppression of Sending-End Transient Overvoltage in A Wind Power Integrated LCC-HVDC System under Commutation Failure. Power and Energy Future. https://doi.org/10.26599/pef.2026.9650018

Vancouver

Wang H, Zhang H, Ma J, Bian J, Guo J. Analysis and Suppression of Sending-End Transient Overvoltage in A Wind Power Integrated LCC-HVDC System under Commutation Failure. Power and Energy Future. 2026. doi:10.26599/pef.2026.9650018

BibTeX
@article{Wang2026,
  author = {Wang, He and Zhang, Han and Ma, Jiajun and Bian, Jing and Guo, Jiazhi},
  title = {Analysis and Suppression of Sending-End Transient Overvoltage in A Wind Power Integrated LCC-HVDC System under Commutation Failure},
  journal = {Power and Energy Future},
  year = {2026},
  doi = {10.26599/pef.2026.9650018}
}
Kostenlos starten →