Purpose
To design, experimentally evaluate, and develop predictive mathematical models for a portable vapour compression refrigeration (VCR) system using R134a refrigerant for localised cooling applications, to improve cooling performance and energy efficiency under varying operating conditions. Design/Methodology/Approach: A portable VCR unit employing R134a refrigerant was designed and tested inside an insulated cooling chamber (6 ft × 6 ft × 6 ft). Experiments varied three operating parameters: cooling load (75, 100, and 200 W), air velocity (1, 1.5, and 2 m/s), and insulation thickness (15, 25, and 40 mm). Response Surface Methodology (RSM) based on a Box–Behnken Design (BBD) with 17 experimental runs was employed to develop predictive models for compressor work, refrigeration effect, condenser capacity, and coefficient of performance (COP). Refrigerant enthalpy values were obtained from the R134a pressure–enthalpy chart to evaluate thermodynamic performance. Research Limitation: The study was conducted under controlled laboratory conditions using a fixed cooling chamber size, which may limit the direct applicability of the findings to larger or different environmental conditions.
Findings
The results indicated that increasing insulation thickness improved refrigeration effect, condenser capacity, and COP while reducing compressor work. Higher air velocity enhanced refrigeration effect, condenser capacity, and COP but also increased compressor work. Increasing cooling load increased compressor work and condenser capacity, whereas refrigeration effect and COP decreased. The developed RSM models demonstrated excellent predictive capability with coefficient of determination (R²) values of 0.9794 for compressor work, 0.9574 for refrigeration effect, 0.9883 for condenser capacity, and 0.9650 for COP. The actual-versus-predicted analysis confirmed the adequacy and reliability of the developed models. Practical Implication: The findings provide useful guidelines for selecting appropriate insulation thickness, air velocity, and cooling load to achieve improved energy efficiency and thermal comfort while reducing overall cooling energy consumption. Social Implication: It can have social value in homes, workplaces, the health sector, temporary cooling applications, and situations where installing full-scale air conditioning is not economically / technically feasible. Originality/ Value: The developed high-accuracy predictive models provide a practical framework for optimising portable refrigeration systems, contributing to the advancement of energy-efficient localised cooling technologies.
Zitieren
APA
Iqbal, M. R. M., & Nanvala, H. (2026). Mathematical Modelling and Performance Analysis of a Portable Vapour Compression Refrigeration System for Localised Cooling Applications. AFRICAN JOURNAL OF APPLIED RESEARCH, 12(8), 76-101. https://doi.org/10.26437/bce0f040
Vancouver
Iqbal MRM, Nanvala H. Mathematical Modelling and Performance Analysis of a Portable Vapour Compression Refrigeration System for Localised Cooling Applications. AFRICAN JOURNAL OF APPLIED RESEARCH. 2026;12(8):76-101. doi:10.26437/bce0f040
BibTeX
@article{Iqbal2026,
author = {Iqbal, M. R. M. and Nanvala, H.},
title = {Mathematical Modelling and Performance Analysis of a Portable Vapour Compression Refrigeration System for Localised Cooling Applications},
journal = {AFRICAN JOURNAL OF APPLIED RESEARCH},
year = {2026},
volume = {12},
number = {8},
pages = {76--101},
doi = {10.26437/bce0f040}
}
EUVIMED