Distance-dependent detection reliability of fixed threshold residual earth-fault indicators in medium-voltage feeders

Ines Bula Bunjaku, Avni Alidemaj, Drenusha Gashi, Donjeta Latifi, Edin Bula

Archives of Electrical Engineering · 18.06.2026 · 1-24

DOI: 10.24425/aee.2026.1525 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Archives of Electrical Engineering, online erschienen am 18.06.2026. Verfasst von Ines Bula Bunjaku und 4 weiteren Autor:innen. Der Volltext ist frei zugänglich (Open Access, CC BY-NC-ND 4.0).

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Residual earth-fault indicators installed in medium-voltage overhead feeders operate with fixed pickup thresholds, while the available residual current decreases with feeder distance. As a result, indicator operation becomes progressively less reliable toward remote feeder sections, and deterministic short-circuit analysis alone is insufficient to cha-racterize practical detectability limits. This study investigates distance-dependent detecta-bility of fixed-threshold residual earth-fault indicators using a combined experimental, si-mulation-based, and probabilistic framework. First, the relay–RTU–SCADA event chain is verified through controlled current-injection testing in a 35 kV reserve feeder bay. Second, residual earth-fault current along the 9.4 km Prizreni 1–Zhuri overhead feeder is evaluated using IEC 60909 single-phase-to-earth simulations implemented in DIgSILENT PowerFac-tory. Probabilistic threshold-exceedance analysis is then applied to estimate detection relia-bility as a function of feeder distance. The simulated residual current decreases from 350.577 A near the source substation to 299.793 A at the feeder endpoint. For the deployed 300 A pickup threshold, the detection probability decreases from near-unity values in upst-ream feeder sections to approximately 0.49 at the remote end of the feeder. Additional sen-sitivity analysis shows that fault resistance, uncertainty level, pickup threshold, and feeder electrical length significantly influence practical detectability limits. The results demon-strate that residual earth-fault indication in long feeders should be evaluated as a probabili-stic distance-dependent problem rather than as a purely deterministic threshold-crossing condition. The presented framework provides an engineering basis for evaluating reliability limits and pickup-threshold adequacy in medium-voltage distribution.

Zitieren

APA

Bunjaku, I. B., Alidemaj, A., Gashi, D., Latifi, D., & Bula, E. (2026). Distance-dependent detection reliability of fixed threshold residual earth-fault indicators in medium-voltage feeders. Archives of Electrical Engineering, 1-24. https://doi.org/10.24425/aee.2026.1525

Vancouver

Bunjaku IB, Alidemaj A, Gashi D, Latifi D, Bula E. Distance-dependent detection reliability of fixed threshold residual earth-fault indicators in medium-voltage feeders. Archives of Electrical Engineering. 2026:1-24. doi:10.24425/aee.2026.1525

BibTeX
@article{Bunjaku2026,
  author = {Bunjaku, Ines Bula and Alidemaj, Avni and Gashi, Drenusha and Latifi, Donjeta and Bula, Edin},
  title = {Distance-dependent detection reliability of fixed threshold residual earth-fault indicators in medium-voltage feeders},
  journal = {Archives of Electrical Engineering},
  year = {2026},
  pages = {1--24},
  doi = {10.24425/aee.2026.1525}
}
Kostenlos starten →