Experimental investigation of a cross-flow heat recovery unit in an air handling unit: energy performance, life cycle assessment, and carbon footprint analysis

Hakan Tutumlu, Cuma Karataş

Dicle Üniversitesi Mühendislik Fakültesi Mühendislik Dergisi · 28.07.2026 · 17 (2)

DOI: 10.24012/dumf.1924722 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Dicle Üniversitesi Mühendislik Fakültesi Mühendislik Dergisi, online erschienen am 28.07.2026. Verfasst von Hakan Tutumlu und 1 weiteren Autor:innen. Die Arbeit nennt 26 Literaturangaben.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Heat recovery units (HRUs) embedded in air handling units (AHUs) represent one of the most straightforward yet effective strategies for curtailing building energy consumption, which accounts for roughly 30-40% of global final energy use. Despite a well-established theoretical foundation, experimental studies spanning multiple operating modes-particularly when combined with life cycle and carbon footprint assessments-remain relatively scarce for cross-flow plate configurations. This paper reports laboratory experiments conducted on the educational Air Handling Unit (AHU) test cycle, which features a cross-flow plate HRU, under four distinct conditioning modes: (1) heating only, (2) humidification combined with heating, (3) cooling with dehumidification, and (4) cooling with dehumidification followed by reheating. Dry-bulb temperature and relative humidity were measured at seven stations along the air path, enabling full psychrometric energy balances following. Air velocity was varied over 1.1-3.6 m/s to assess its influence on HRU temperature effectiveness ( ), thermal output, and Coefficient of Performance (COP). Results show that decreases from 0.792 to 0.671 as velocity increases in heating mode, while the fraction of total heating demand covered by heat recovery reaches 129% at the highest velocity tested. COP of cooling ranges from 2.52 to 3.37 in Mode 3 and rises to 3.21-5.04 in Mode 4. A simplified operational life cycle assessment (ISO 14040:2006; ISO 14044:2006) using Turkey’s national grid emission factor (0.452 kgCO₂eq/kWh) yields annual CO₂ savings of approximately 6,136 kgCO₂eq.

Zitieren

APA

Tutumlu, H., & Karataş, C. (2026). Experimental investigation of a cross-flow heat recovery unit in an air handling unit: energy performance, life cycle assessment, and carbon footprint analysis. Dicle Üniversitesi Mühendislik Fakültesi Mühendislik Dergisi, 17(2). https://doi.org/10.24012/dumf.1924722

Vancouver

Tutumlu H, Karataş C. Experimental investigation of a cross-flow heat recovery unit in an air handling unit: energy performance, life cycle assessment, and carbon footprint analysis. Dicle Üniversitesi Mühendislik Fakültesi Mühendislik Dergisi. 2026;17(2). doi:10.24012/dumf.1924722

BibTeX
@article{Tutumlu2026,
  author = {Tutumlu, Hakan and Karataş, Cuma},
  title = {Experimental investigation of a cross-flow heat recovery unit in an air handling unit: energy performance, life cycle assessment, and carbon footprint analysis},
  journal = {Dicle Üniversitesi Mühendislik Fakültesi Mühendislik Dergisi},
  year = {2026},
  volume = {17},
  number = {2},
  doi = {10.24012/dumf.1924722}
}
Kostenlos starten →