Research on applicability and optimization of solar-dual-source heat pump hybrid heating systems in severely cold regions

Qi Zhao, Bo Tian, Bowen Chu, Yingcheng Wang, Fayv Wu, Haotian Hu

Thermal Science · 2026 · (00) · 95-95

DOI: 10.2298/tsci260101095z ↗

Kurz gefasst

Fachartikel in der Zeitschrift Thermal Science, 2026. Verfasst von Qi Zhao und 5 weiteren Autor:innen. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

This study proposes a solar-dual-source (ground source + air source) heat pump hybrid heating system. Targeting the heating needs of severely cold regions, a typical office building in Harbin was used as the model. Hourly simulation models of three systems-independent ground source heat pump, solar-ground source heat pump, and solar-dual-source heat pump-were constructed using TRNSYS software. The system prioritizes solar energy for cross-seasonal heat storage, with an air source heat pump as an auxiliary system and a ground source heat pump as a backup. A quality-adjusted variable water supply temperature strategy is employed. Ten-year simulations show that the soil temperature decreased by 6.88℃ with the independent ground source heat pump system, by 1.25℃ with the solar-ground source heat pump system, and by a slight increase of 0.25℃ with the solar-dual-source heat pump system. The Hybrid Genetic Particle Swarm Optimization Algorithm was used to perform multi-objective optimization of nine parameters, including collector area, hot water storage tank volume, air source heat pump capacity, buried pipe depth, and key control temperature difference. After optimization, the COP of both ground-source and air-source heat pumps improved, the collector outlet temperature increased by approximately 33%, and overall energy efficiency was significantly improved. In a comprehensive assessment of energy, economic, and environmental benefits, the system demonstrated clear advantages, providing a reliable solution for low-carbon heating in frigid regions.

Zitieren

APA

Zhao, Q., Tian, B., Chu, B., Wang, Y., Wu, F., & Hu, H. (2026). Research on applicability and optimization of solar-dual-source heat pump hybrid heating systems in severely cold regions. Thermal Science, 95-95. https://doi.org/10.2298/tsci260101095z

Vancouver

Zhao Q, Tian B, Chu B, Wang Y, Wu F, Hu H. Research on applicability and optimization of solar-dual-source heat pump hybrid heating systems in severely cold regions. Thermal Science. 2026:95-95. doi:10.2298/tsci260101095z

BibTeX
@article{Zhao2026,
  author = {Zhao, Qi and Tian, Bo and Chu, Bowen and Wang, Yingcheng and Wu, Fayv and Hu, Haotian},
  title = {Research on applicability and optimization of solar-dual-source heat pump hybrid heating systems in severely cold regions},
  journal = {Thermal Science},
  year = {2026},
  number = {00},
  pages = {95--95},
  doi = {10.2298/tsci260101095z}
}
Kostenlos starten →