Optimal Siting and Sizing of EV Charging Stations in Distribution Networks Using the Grey Wolf Optimizer
International Journal of Computational and Experimental Science and Engineering · 28.06.2026 · 12 (3)
DOI: 10.22399/ijcesen.5367 ↗Kurz gefasst
Fachartikel in der Zeitschrift International Journal of Computational and Experimental Science and Engineering, online erschienen am 28.06.2026. Verfasst von Amal Menasria und 4 weiteren Autor:innen. Die Arbeit nennt 24 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).
Abstract (Originalsprache)
This study addresses the optimal siting and sizing of Electric Vehicle Charging Stations (EVCSs) in a 30-bus radial distribution network using the Grey Wolf Optimizer (GWO). The problem is formulated as a multi-objective optimization task that simultaneously minimizes total investment cost, reduces active and reactive power losses, and improves the voltage profile across the network. These objectives are combined into a single weighted-sum cost function controlled by three weighting coefficients (w₁, w₂, w₃), subject to operational constraints including nodal voltage limits, power balance equations, and charger deployment bounds. Nine weighting configurations are tested to assess the influence of each coefficient on solution quality and infrastructure deployment scale. Results show that the configuration (w₁ = 0.1, w₂ = 0.6, w₃ = 0.3) achieves the best overall performance, yielding a minimum objective function value of 209,911.20 with 28 deployed charging stations, striking an effective balance between economic investment and technical efficiency. The GWO algorithm demonstrated rapid convergence in fewer than 20 iterations across all tested cases, with stable and consistent behavior free from noticeable oscillations. The analysis further reveals that assigning a higher weight to active power loss reduction (w₂ ≥ 0.5) consistently produces superior optimization outcomes, while increasing the investment weight promotes a more conservative deployment strategy with fewer installed stations. In all configurations, bus voltages remained within acceptable operating limits, confirming that the proposed optimization strategy preserves grid stability during EVCS integration. These findings establish GWO as a reliable and computationally efficient tool for EV charging infrastructure planning in modern distribution systems.
Zitieren
APA
Menasria, A., Abdelkhalek, O., Gasbaoui, B., Hamouda, M., & Bouzidi, M. (2026). Optimal Siting and Sizing of EV Charging Stations in Distribution Networks Using the Grey Wolf Optimizer. International Journal of Computational and Experimental Science and Engineering, 12(3). https://doi.org/10.22399/ijcesen.5367
Vancouver
Menasria A, Abdelkhalek O, Gasbaoui B, Hamouda M, Bouzidi M. Optimal Siting and Sizing of EV Charging Stations in Distribution Networks Using the Grey Wolf Optimizer. International Journal of Computational and Experimental Science and Engineering. 2026;12(3). doi:10.22399/ijcesen.5367
BibTeX
@article{Menasria2026,
author = {Menasria, Amal and Abdelkhalek, Othmane and Gasbaoui, Brahim and Hamouda, Messaoud and Bouzidi, Mohammed},
title = {Optimal Siting and Sizing of EV Charging Stations in Distribution Networks Using the Grey Wolf Optimizer},
journal = {International Journal of Computational and Experimental Science and Engineering},
year = {2026},
volume = {12},
number = {3},
doi = {10.22399/ijcesen.5367}
}
EUVIMED