Mitigating Legionella spp. risk in an Australian healthcare facility using on-site electrochemical water disinfection
Journal of Water and Health · 2025
DOI: 10.2166/wh.2025.395 ↗Kurz gefasst
Fachartikel in der Zeitschrift Journal of Water and Health, 2025. Verfasst von Sopheak Hem und 8 weiteren Autor:innen. Beteiligte Einrichtung: Future Industries Institute, University of South Australia, Mawson Lakes, South Australia, Australia. Hauptthemen laut MEDLINE: Legionella, Disinfection, Water Microbiology, Water Purification. Die Arbeit wurde bisher 1-mal zitiert (Crossref) und nennt 47 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).
Abstract (Originalsprache)
Legionella spp. are Gram-negative bacteria present in natural and engineered water systems that can cause legionellosis (Legionnaires' disease and Pontiac fever). When present in biofilms of healthcare facilities, they are a likely source of legionellosis for immunocompromised patients. The objective of this study was to evaluate an electrochemical water disinfection system to produce and dose hypochlorous acid (HOCl) to reduce this risk in a hospital with systemic Legionella spp. contamination. Furthermore, Legionella spp. colony counts were compared to quantitative polymerase chain reaction (qPCR) results. Before and after implementing the disinfection system, tap water and pipe biofilms were analysed for microbial contamination. Post-implementation monitoring continued for over six months, assessing microbial quality using heterotrophic colony counts, Legionella serotyping, and qPCR targeting total bacteria (16S rRNA) and Legionella spp. By the third sampling event (22 days post-commissioning), water quality consistently improved, with no culture-positive Legionella counts observed thereafter. qPCR analysis confirmed these results, proving more sensitive and reliable than traditional methods. The qPCR assays for Legionella spp. and bacterial 16S rRNA were also cost-effective for system optimisation and diagnostics.
Schlagwörter
MeSH-Schlagwörter (MEDLINE)
Stichwörter der Autor:innen
Substanzen
Autor:innen und Institutionen
- Future Industries Institute, University of South Australia, Mawson Lakes, South Australia, Australia.
- CRC SAAFE (Cooperative Research Centre for Solving Antimicrobial Resistance in Agribusiness, Food, and Environments) Cooperative Research Centre for Solving Antimicrobial Resistance in Agribusiness, Food, and Environmen…
- UniSA STEM, University of South Australia, Adelaide, SA, Australia.
- Department of Biochemistry and Biotechnology, Laboratory of Plant and Environmental Biotechnology, University of Thessaly, Larissa, Viopolis 41500, Greece.
- Department of Agricultural, Food and Environmental Sciences, Polytechnic University of Marche, Via Brecce Bianche, 60131 Ancona, Italy.
- Ecas4 Australia Pty Ltd, 8/1 London Road, Mile End South, South Australia, Australia.
ORCID-Profile: Sopheak Hem, Barbara Drigo, Sotirios Vasileiadis, Gianluca Brunetti, Euan Smith, Enzo Lombi, Nicholas J Ashbolt, Erica Donner
Zitieren
APA
Hem, S., Drigo, B., Vasileiadis, S., Brunetti, G., Smith, E., Ferro, S., Lombi, E., Ashbolt, N. J., & Donner, E. (2025). Mitigating Legionella spp. risk in an Australian healthcare facility using on-site electrochemical water disinfection. Journal of Water and Health. https://doi.org/10.2166/wh.2025.395
Vancouver
Hem S, Drigo B, Vasileiadis S, Brunetti G, Smith E, Ferro S, et al. Mitigating Legionella spp. risk in an Australian healthcare facility using on-site electrochemical water disinfection. Journal of Water and Health. 2025. doi:10.2166/wh.2025.395
BibTeX
@article{Hem2025,
author = {Hem, Sopheak and Drigo, Barbara and Vasileiadis, Sotirios and Brunetti, Gianluca and Smith, Euan and Ferro, Sergio and Lombi, Enzo and Ashbolt, Nicholas J and Donner, Erica},
title = {Mitigating Legionella spp. risk in an Australian healthcare facility using on-site electrochemical water disinfection},
journal = {Journal of Water and Health},
year = {2025},
doi = {10.2166/wh.2025.395}
}
EUVIMED