Abstract (Originalsprache)

R32 refrigerant has attracted increasing attention as a more environmentally friendly and efficient alternative to R404a, R407a, and R507a in low‑temperature cold storage applications. This study evaluates the performance of R32 in a cold storage system, beginning at an ambient temperature of 32 °C and continuing until the chamber reaches −18 °C to −20 °C, with evaporator temperatures down to −28 °C. The methodology combines steady‑state simulations conducted via an Excel VBA interface (“The Poci”) with experimental validation using a standard cold-storage setup (compressor, condenser, expansion valve, and evaporator). Test conditions included ambient temperatures of 25 °C, 30 °C, 35 °C, and 40 °C, and condensing temperatures of 45 °C, 50 °C, 55 °C, and 60 °C. Temperature and pressure were recorded every minute using K‑type thermocouples and pressure transmitters; compressor power consumption was logged with a power‑meter data logger; and mass flow rates were measured with a Coriolis data logger. Model validation employed the Mean Absolute Percentage Error (MAPE). Results show a MAPE deviation of 2.11 %, indicating high simulation accuracy. At a constant cooling load, R32 achieved the lowest compressor power consumption (0.65–0.68 kW) and the highest coefficient of performance (COP = 2.8) among the refrigerants. Lowering the condensing temperature improved the thermal efficiency of all refrigerants, but R32 remained superior, particularly under ambient conditions of 30 °C–35 °C. Pressure–enthalpy (P–h) diagram analysis confirmed that R32 exhibits a higher evaporation enthalpy and a shorter compression path, contributing to its superior COP. These findings demonstrate that R32 is highly suitable for cold storage applications at −18 °C to −20 °C, replacing R404a, R407a, and R507a, offering enhanced energy efficiency and potential reductions in global warming potential (GWP). Further research is recommended to conduct long‑term studies on refrigerant–material compatibility and to perform fire risk assessments associated with R32’s A2L flammability classification.

Zitieren

APA

Suhengki, Manik, H. M., Hestirianoto, T., Susilohadi, & Yulianto, M. (2026). Performance Parameter Study of R32 for Low Temperature Cold Storage. International Journal on Advanced Science, Engineering and Information Technology, 16(2), 663-671. https://doi.org/10.18517/ijaseit.16.2.20836

Vancouver

Suhengki, Manik HM, Hestirianoto T, Susilohadi, Yulianto M. Performance Parameter Study of R32 for Low Temperature Cold Storage. International Journal on Advanced Science, Engineering and Information Technology. 2026;16(2):663-671. doi:10.18517/ijaseit.16.2.20836

BibTeX
@article{Suhengki2026,
  author = {Suhengki and Manik, Henry M. and Hestirianoto, Totok and Susilohadi and Yulianto, M.},
  title = {Performance Parameter Study of R32 for Low Temperature Cold Storage},
  journal = {International Journal on Advanced Science, Engineering and Information Technology},
  year = {2026},
  volume = {16},
  number = {2},
  pages = {663--671},
  doi = {10.18517/ijaseit.16.2.20836}
}
Kostenlos starten →