EUVIMEDEUVIMED entdecken
Crossref

Investigating Safety Standards and Performance of Emergency Power Diesel Generators in Hospitals of Tabriz, Iran

Djavad Ghoddoosi-Nejad, Amin Daemi, Ali Janati, Rouhollah Yaghoubi

Health Technology Assessment in Action · 01.08.2021

DOI: 10.18502/htaa.v4i4.6863 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Health Technology Assessment in Action, online erschienen am 01.08.2021. Verfasst von Djavad Ghoddoosi-Nejad und 3 weiteren Autor:innen. Die Arbeit wurde bisher 1-mal zitiert (Crossref).

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Background

Power outage risk is one of the serious risks that could be eliminated by supplying electricity through the emergency power system installed in a hospital, such as diesel generators and uninterruptible power supplies (UPSs).

Objectives

The present study aimed to investigate the observance of safety and maintenance standards of emergency power diesel generators in the hospitals of Tabriz.

Methods

This descriptive-analytical research was cross-sectionally performed in 18 hospitals of Tabriz in 2014. The data collection tools included a questionnaire and a checklist prepared according to the national standards and consisted of 87 questions in 15 categories. Data were analyzed using SPSS version 19.

Results

The average rates of observance of safety and maintenance standards of diesel generators in 111-question standards and 87-question standards were equal to 61.4 and 52.8%, respectively. Regarding the observance of the 19 standards, “ventilation” and “daily visits” standards with 28.94 and 96.24, respectively, had the lowest and highest degrees of observance in hospitals. There was a significant direct association between observing the standards defined for diesel generators with the number of hospital beds (P = 0.01) and the total capacity of emergency power generation by generators (P = 0.05).

Conclusions

The results of the present study indicate a low level of safety and maintenance for the emergency power systems of hospitals. These scores are not considered favorable for a system called “emergency”, and if the necessary interventions are not made in this regard, in the event of natural disasters and human errors, hospitals will face numerous problems.

Zitieren

APA

Ghoddoosi-Nejad, D., Daemi, A., Janati, A., & Yaghoubi, R. (2021). Investigating Safety Standards and Performance of Emergency Power Diesel Generators in Hospitals of Tabriz, Iran. Health Technology Assessment in Action. https://doi.org/10.18502/htaa.v4i4.6863

Vancouver

Ghoddoosi-Nejad D, Daemi A, Janati A, Yaghoubi R. Investigating Safety Standards and Performance of Emergency Power Diesel Generators in Hospitals of Tabriz, Iran. Health Technology Assessment in Action. 2021. doi:10.18502/htaa.v4i4.6863

BibTeX
@article{GhoddoosiNejad2021,
  author = {Ghoddoosi-Nejad, Djavad and Daemi, Amin and Janati, Ali and Yaghoubi, Rouhollah},
  title = {Investigating Safety Standards and Performance of Emergency Power Diesel Generators in Hospitals of Tabriz, Iran},
  journal = {Health Technology Assessment in Action},
  year = {2021},
  doi = {10.18502/htaa.v4i4.6863}
}
Kostenlos starten →