Voltage Stability Analysis of Low-Voltage Distribution Networks with High Penetration of Rooftop PV Systems
Journal of Daylighting · 2026-12 · 13 (2) · 770-792
DOI: 10.15627/jd.2026.41 ↗Kurz gefasst
Fachartikel in der Zeitschrift Journal of Daylighting, 2026-12. Verfasst von Omar Kanaan Al Basri und 2 weiteren Autor:innen.
Abstract (Originalsprache)
The paper presents a study on the effect of increasing rooftop PV penetration on voltage stability of low-voltage (LV) radial distribution feeders. A 12-bus European-style LV feeder modeled using the CIGRE benchmark parameters with NAYY 4×35 mm² aluminium underground cable is considered at 400 V/50 Hz. The Backward-Forward Sweep (BFS) algorithm is applied for load flow analysis under six different PV penetration cases from 0% to 100% (the PV penetration factor ρ is defined throughout as the fraction of the feeder’s aggregate rooftop-PV capacity that is in service, each of the eleven load buses being equipped with a PV unit rated at 110% of its own peak active load, so that ρ = 100% corresponds to 62.70 kWp of installed PV against a 57.00 kW feeder peak demand) with 24-hour residential load and clear-sky solar irradiance data. The voltage stability indices like Fast Voltage Stability Index (FVSI), Voltage Stability Index (VSI) and Voltage Deviation Index (VDI) are used and the results are compared against the EN 50160 limit for power quality. It is observed that the PV penetration decreases the active power losses gradually and up to 41.4% as compared to the base case. However, it also causes an overvoltage violation at Bus 11, where the maximum bus voltage reaches 1.1092 pu, exceeding the EN 50160 upper limit of 1.10 pu by 0.92%. VDI shows a non-monotonic behavior with the PV penetration and has its minimum value of 0.0631 pu at 60% penetration level, thus representing the same as an optimal operating point. Furthermore, FVSI and VSI indicate that voltage collapse is not the issue of concern in all the cases, while the power quality is the new limit. The power-flow implementation is verified against three relations that follow analytically from the model equations, and a mitigation assessment shows that, because the resistance-to-reactance ratio of the NAYY 4×35 mm² cable is 10.59, reactive Volt-VAr control is an intrinsically inefficient countermeasure on this feeder — restoring compliance by reactive absorption alone would require an inverter apparent-power rating 1.93 times the active rating — whereas a 0.025 pu reduction of the transformer set-point in the midday hours, a 15.5% curtailment of the exported surplus, or distributed battery storage each restore full EN 50160 compliance at 100% penetration.
Zitieren
APA
Basri, O. K. A., Nori, F. K., & Hussein, M. A. (2026). Voltage Stability Analysis of Low-Voltage Distribution Networks with High Penetration of Rooftop PV Systems. Journal of Daylighting, 13(2), 770-792. https://doi.org/10.15627/jd.2026.41
Vancouver
Basri OKA, Nori FK, Hussein MA. Voltage Stability Analysis of Low-Voltage Distribution Networks with High Penetration of Rooftop PV Systems. Journal of Daylighting. 2026;13(2):770-792. doi:10.15627/jd.2026.41
BibTeX
@article{Basri2026,
author = {Basri, Omar Kanaan Al and Nori, Fayrooz Kanaan and Hussein, Mohammed Abdulridha},
title = {Voltage Stability Analysis of Low-Voltage Distribution Networks with High Penetration of Rooftop PV Systems},
journal = {Journal of Daylighting},
year = {2026},
volume = {13},
number = {2},
pages = {770--792},
doi = {10.15627/jd.2026.41}
}
EUVIMED