Optimal design and operation of Photovoltage distributed generators and shunt compensators for the Vietnam alternative current distribution network to reduce annual energy loss
PLOS One · 02.03.2026 · 21 (3) · e0342402
DOI: 10.1371/journal.pone.0342402 ↗Kurz gefasst
Fachartikel in der Zeitschrift PLOS One, online erschienen am 02.03.2026. Verfasst von Minh Phuc Duong und 3 weiteren Autor:innen. Beteiligte Einrichtung: Power System Optimization Research Group, Faculty of Electrical and Electronics Engineering, Ton Duc Thang University, Ho Chi Minh City, Vietnam. Hauptthemen laut MEDLINE: Electric Power Supplies, Solar Energy. Die Arbeit wurde bisher 1-mal zitiert (Crossref) und nennt 79 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Ho Chi Minh City University of Technology and Education.
Abstract (Originalsprache)
This study presents the application of two novel meta-heuristic algorithms, including the Fungal Growth Optimizer (FGO) and Animated Oat Optimization Algorithm (AOO), to optimize the placement of DGs and SCBs for power loss reduction in three alternative current distribution networks (ACDNs), including a practical ACDN with 55 nodes in Vietnam, besides the two IEEE standard ACDNs. In the study, placement of DGs and SCBs on the three grids is conducted in two phases, including the designing phase and the operational phase. In the designing phase, DGs and SCBs were optimized in their placement on the grids by the two algorithms in various scenarios with different DG configurations. The results achieved through scenarios indicate that AOO completely outperforms FGO in terms of the optimal total active power loss values (TAPL) and the stability of the outputs. Particularly, in the two scenarios conducted on the IEEE 69-node, the TAPL achieved by AOO is better than FGO, 3.65% for the first scenario and 72.28% for the second scenario. In the other two scenarios conducted on the IEEE 85-node, AOO still proves its high effectiveness over FGO by reaching the better TAPL at 6.02% in Scenario 1 and 44.88% in Scenario 2. Lastly, AOO is continuously superior to FGO in the four scenarios in the Vietnam ACDN, with 55-node by 1.04% in Scenario 1, 19.52% in Scenario 2, 7.07% in Scenario 3, and 69.60% in Scenario 4. Next in the operational phase, AOO is reapplied to optimize the power output of PVDGs and SCBs within an average day of the first month in the four quarters of the year, with load demand variation and dynamic supplied power from PVDGs in four scenarios with different settings of PVDGs and SCBs. The results clearly reveal that the operational Scenario 4 with PVDGs is configured to supply both active and reactive power to the grid, along with SCBs, which offer the best value of energy loss in the three quarters, except for the third one, where the operational Scenario 2 is the most suited for energy loss.
Schlagwörter
MeSH-Schlagwörter (MEDLINE)
Autor:innen und Institutionen
- Power System Optimization Research Group, Faculty of Electrical and Electronics Engineering, Ton Duc Thang University, Ho Chi Minh City, Vietnam.
- Faculty of Electrical and Electronics Engineering, Ho Chi Minh City University of Technology and Engineering, Ho Chi Minh City, Vietnam.
- Buryat Institute of Infocommunications, Siberian State University of Telecommunications and Information Science, Novosibirsk, Russia.
ORCID-Profile: Minh Phuc Duong, Bon Nhan Nguyen
Förderung
- Ho Chi Minh City University of Technology and Education
Zitieren
APA
Duong, M. P., Nguyen, B. N., Arkhincheev, V., & Nguyen, T. T. (2026). Optimal design and operation of Photovoltage distributed generators and shunt compensators for the Vietnam alternative current distribution network to reduce annual energy loss. PLOS One, 21(3), e0342402. https://doi.org/10.1371/journal.pone.0342402
Vancouver
Duong MP, Nguyen BN, Arkhincheev V, Nguyen TT. Optimal design and operation of Photovoltage distributed generators and shunt compensators for the Vietnam alternative current distribution network to reduce annual energy loss. PLOS One. 2026;21(3):e0342402. doi:10.1371/journal.pone.0342402
BibTeX
@article{Duong2026,
author = {Duong, Minh Phuc and Nguyen, Bon Nhan and Arkhincheev, Valeriy and Nguyen, Thang Trung},
title = {Optimal design and operation of Photovoltage distributed generators and shunt compensators for the Vietnam alternative current distribution network to reduce annual energy loss},
journal = {PLOS One},
year = {2026},
volume = {21},
number = {3},
pages = {e0342402},
doi = {10.1371/journal.pone.0342402}
}