High‐Impedance Fault Detection in Electric Power Distribution Network Using Local Pattern Transformation Methods and Bidirectional Long Short–Term Memory
Journal of Electrical and Computer Engineering · 2025-01 · 2025 (1)
DOI: 10.1155/jece/3310174 ↗Kurz gefasst
Fachartikel in der Zeitschrift Journal of Electrical and Computer Engineering, online erschienen am 09.01.2025. Verfasst von Rini Varghese P und 7 weiteren Autor:innen. Die Arbeit wurde bisher 3-mal zitiert (Crossref) und nennt 41 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).
Abstract (Originalsprache)
The high‐impedance fault (HIF) occurring in medium voltage (MV) distribution networks is dangerous to livestock and personnel due to its arcing nature. The untimely detection of the fault can endanger lives and destroy equipment. Identifying the occurrence of HIF in a power system is a cumbersome task, as fault current falls within the normal current range. The paper analyses current signals from radial and mesh distribution networks and features extracted during HIF and non‐HIF conditions by using the local binary pattern (LBP), local neighbor gradient pattern (LNGP), local neighbor descriptive pattern (LNDP), and local gradient pattern (LGP). In the proposed algorithm, 1D signal analysis for HIF detection in the MV distribution system is performed for the first time for fault analysis. The Kruskal–Wallis test was carried out to get the best feature sets from the extracted features. HIF and non‐HIF were classified by bidirectional long short–term memory (Bi‐LSTM) for the selected feature sets. Among the four algorithms, LGP attains the best accuracy for both networks; hence, the paper recommends that LGP with Bi‐LSTM is more effective for detecting HIF occurrence.
Zitieren
APA
P, R. V., Subathra, M. S. P., George, S. T., Peter, G., Stonier, A. A., N, S., A, A., & Ganji, V. (2025). High‐Impedance Fault Detection in Electric Power Distribution Network Using Local Pattern Transformation Methods and Bidirectional Long Short–Term Memory. Journal of Electrical and Computer Engineering, 2025(1). https://doi.org/10.1155/jece/3310174
Vancouver
P RV, Subathra MSP, George ST, Peter G, Stonier AA, N S, et al. High‐Impedance Fault Detection in Electric Power Distribution Network Using Local Pattern Transformation Methods and Bidirectional Long Short–Term Memory. Journal of Electrical and Computer Engineering. 2025;2025(1). doi:10.1155/jece/3310174
BibTeX
@article{P2025,
author = {P, Rini Varghese and Subathra, M. S. P. and George, S. Thomas and Peter, Geno and Stonier, Albert Alexander and N, Sairamya and A, Ananthi and Ganji, Vivekananda},
title = {High‐Impedance Fault Detection in Electric Power Distribution Network Using Local Pattern Transformation Methods and Bidirectional Long Short–Term Memory},
journal = {Journal of Electrical and Computer Engineering},
year = {2025},
volume = {2025},
number = {1},
doi = {10.1155/jece/3310174}
}
EUVIMED