Fachartikel in der Zeitschrift Indoor Air, online erschienen am 08.01.2025. Verfasst von Young Jae Choi und 5 weiteren Autor:innen. Die Arbeit wurde bisher 11-mal zitiert (Crossref) und nennt 48 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Ministry of Science, ICT and Future Planning, National Research Foundation of Korea, Ministry of Trade, Industry and Energy.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

This study developed and evaluated an optimal ventilation strategy for variable air volume (VAV) systems, targeting carbon dioxide (CO 2 ) and particulate matter less than 2.5 μ m in diameter (PM 2.5 ) concentrations. The strategy integrates system‐level demand‐controlled ventilation (DCV) based on real‐time occupancy data and zone‐level predictive control using indoor air quality (IAQ) prediction models. By predicting indoor CO 2 and PM 2.5 levels for the subsequent time step and dynamically adjusting control priorities, optimal airflow is determined. A co‐simulation model integrating EnergyPlus, CONTAM, and Python was employed for model training and testing. The proposed strategy was compared with on–off control, CO 2 predictive control, and PM 2.5 predictive control, demonstrating superior prediction accuracy and stable IAQ maintenance. The optimal ventilation strategy achieved the highest performance, maintaining CO 2 and PM 2.5 levels below their respective upper limits of 100% and 97.33% of the time. Although this strategy resulted in slightly higher energy consumption compared to the other control algorithms due to its multivariable control approach, it effectively maintained IAQ standards. This method simplifies development and maintenance by circumventing the need for complex optimization, providing a flexible and cost‐effective solution for IAQ management. Future research will focus on developing integrated VAV system control strategies that ensure comfort year‐round, addressing both energy efficiency and thermal comfort.

Förderung

  • Ministry of Science, ICT and Future Planning
  • National Research Foundation of Korea
  • Ministry of Trade, Industry and Energy
  • Korea Institute of Energy Technology Evaluation and Planning

Zitieren

APA

Choi, Y. J., Choi, E. J., Byun, J. Y., Moon, H. J., Sung, M. K., & Moon, J. W. (2025). CO 2 ‐ and PM 2.5 ‐Focused Optimal Ventilation Strategy Based on Predictive Control. Indoor Air, 2025(1). https://doi.org/10.1155/ina/6652442

Vancouver

Choi YJ, Choi EJ, Byun JY, Moon HJ, Sung MK, Moon JW. CO 2 ‐ and PM 2.5 ‐Focused Optimal Ventilation Strategy Based on Predictive Control. Indoor Air. 2025;2025(1). doi:10.1155/ina/6652442

BibTeX
@article{Choi2025,
  author = {Choi, Young Jae and Choi, Eun Ji and Byun, Jae Yoon and Moon, Hyeun Jun and Sung, Min Ki and Moon, Jin Woo},
  title = {CO 2 ‐ and PM 2.5 ‐Focused Optimal Ventilation Strategy Based on Predictive Control},
  journal = {Indoor Air},
  year = {2025},
  volume = {2025},
  number = {1},
  doi = {10.1155/ina/6652442}
}
Kostenlos starten →