Effect of Filter Characteristics on Particulate Matter Reduction in Residential Ventilation Systems

Se H. Lim, Jin C. Park, Yong W. Song

Indoor Air · 2026-01 · 2026 (1)

DOI: 10.1155/ina/6069251 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Indoor Air, online erschienen am 22.11.2026. Verfasst von Se H. Lim und 2 weiteren Autor:innen. Die Arbeit nennt 46 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: National Research Foundation of Korea.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

The fine particulate matter (PM 2.5 ) reduction performance of mechanical ventilation systems is often assessed solely based on the filtration efficiency of the installed filters. However, because these systems comprise multiple mechanical components, it is crucial to evaluate the PM 2.5 reduction capability of the entire ventilation unit rather than that of the filter alone. Moreover, limited research has examined how variations in filter thickness influence system performance under different PM 2.5 concentration conditions. This study addresses this gap by experimentally investigating the PM 2.5 reduction performance of mechanical ventilation systems through the use of dust‐collection filters of different types and thicknesses, utilizing artificially generated PM 2.5 . The suitability of the artificial PM 2.5 source was verified through scanning mobility particle sizer (SMPS) analysis. A reduction time model was also proposed to estimate the duration required for PM 2.5 removal based on indoor PM 2.5 generation, enabling prediction of system performance and response time. In addition, an accelerated aging experiment was conducted to estimate the filter replacement cycle under varying PM 2.5 conditions. The results showed that even under fluctuating atmospheric PM 2.5 levels, a 30T HEPA filter achieved effective PM 2.5 mass reduction, with removal efficiencies of 94.4%–98.8%. The estimated filter replacement interval was approximately 526 days (395–789 days) under the 2024 ambient PM 2.5 distribution and should be regarded as an upper bound. This study provides foundational data for filter selection and maintenance strategies, contributing to cleaner indoor environments and more sustainable ventilation system design for residential buildings.

Förderung

  • National Research Foundation of Korea

Zitieren

APA

Lim, S. H., Park, J. C., & Song, Y. W. (2026). Effect of Filter Characteristics on Particulate Matter Reduction in Residential Ventilation Systems. Indoor Air, 2026(1). https://doi.org/10.1155/ina/6069251

Vancouver

Lim SH, Park JC, Song YW. Effect of Filter Characteristics on Particulate Matter Reduction in Residential Ventilation Systems. Indoor Air. 2026;2026(1). doi:10.1155/ina/6069251

BibTeX
@article{Lim2026,
  author = {Lim, Se H. and Park, Jin C. and Song, Yong W.},
  title = {Effect of Filter Characteristics on Particulate Matter Reduction in Residential Ventilation Systems},
  journal = {Indoor Air},
  year = {2026},
  volume = {2026},
  number = {1},
  doi = {10.1155/ina/6069251}
}
Kostenlos starten →