Centralised Air Sampling From a Ventilation System for the Surveillance of Respiratory Pathogens
Indoor Air · 2024-01 · 2024 (1)
DOI: 10.1155/2024/5176619 ↗Kurz gefasst
Fachartikel in der Zeitschrift Indoor Air, online erschienen am 18.10.2024. Verfasst von Michiel Happaerts und 11 weiteren Autor:innen. Die Arbeit wurde bisher 7-mal zitiert (Crossref) und nennt 24 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Fonds Wetenschappelijk Onderzoek, KU Leuven.
Abstract (Originalsprache)
Background
The COVID‐19 pandemic has triggered a renewed interest in indoor air sampling for infectious disease surveillance. However, scalability is currently limited, as samples are usually collected in a single indoor space. An alternative is to place the device within a heating, ventilation, and air conditioning system (HVAC), but this approach has not been tested against room air sampling.
Methods
In this observational study, we sampled the air in an indoor fitness centre for 2 or 6 h, simultaneously in three locations of the main exercise hall and in the return plenum of the HVAC system. Samples were collected twice weekly for 11 weeks. All samples were tested for 29 respiratory pathogens using PCR. We compared the ventilation system and exercise hall air with regard to the presence and quantity of pathogens.
Findings
Samples collected in two locations in the exercise hall had a similar overall sensitivity to the HVAC sampler for detecting pathogens, while a third sampling location was associated with significantly lower sensitivity. Overall, the pathogen concentration was similar in the ventilation system and the exercise hall air (ratio: 1.0; 95% CI: 0.8–1.3).
Interpretation
Our results show that air sampling within a ventilation system can have equal sensitivity for detecting respiratory pathogens, compared to room‐based sampling. Thus, placing samplers within central ventilation systems could increase the scalability of air sampling for infectious disease surveillance.
Förderung
- Fonds Wetenschappelijk Onderzoek
- KU Leuven
Zitieren
APA
Happaerts, M., Geenen, C., Michiels, J., Gorissen, S., Swinnen, J., Beuselinck, K., Laenen, L., Raymenants, J., Lorent, N., Ombelet, S., Keyaerts, E., & André, E. (2024). Centralised Air Sampling From a Ventilation System for the Surveillance of Respiratory Pathogens. Indoor Air, 2024(1). https://doi.org/10.1155/2024/5176619
Vancouver
Happaerts M, Geenen C, Michiels J, Gorissen S, Swinnen J, Beuselinck K, et al. Centralised Air Sampling From a Ventilation System for the Surveillance of Respiratory Pathogens. Indoor Air. 2024;2024(1). doi:10.1155/2024/5176619
BibTeX
@article{Happaerts2024,
author = {Happaerts, Michiel and Geenen, Caspar and Michiels, Jade and Gorissen, Sarah and Swinnen, Jens and Beuselinck, Kurt and Laenen, Lies and Raymenants, Joren and Lorent, Natalie and Ombelet, Sien and Keyaerts, Els and André, Emmanuel},
title = {Centralised Air Sampling From a Ventilation System for the Surveillance of Respiratory Pathogens},
journal = {Indoor Air},
year = {2024},
volume = {2024},
number = {1},
doi = {10.1155/2024/5176619}
}
EUVIMED