EUVIMEDEUVIMED entdecken
Crossref

REALIZATION OF HIGH IPF ICE SLURRY FOR DISTRICT COOLING

YOON PYO LEE, SANG HOON LEE, HOSEON YOO

International Journal of Air-Conditioning and Refrigeration · 2010

DOI: 10.1142/s2010132510000149 ↗

Kurz gefasst

Fachartikel in der Zeitschrift International Journal of Air-Conditioning and Refrigeration, 2010. Verfasst von YOON PYO LEE und 2 weiteren Autor:innen. Die Arbeit wurde bisher 2-mal zitiert (Crossref) und nennt 6 Literaturangaben.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

The Production of high IPF (ice packing factor) ice slurry was realized. The ice slurry maker which can efficiently produce ice slurry under ice particles in-flowing condition was revised. We removed the stagnant region at the top of the ice slurry maker, thereby high IPF ice slurry was realized. The IPF controller with 6 mm diameter holes could not control IPF in a pipe. This is because ice particles in ice slurry flow exist homogeneously not only at the upper part but also at the bottom part. We changed the hole size at the surface of the IPF controller by means of fine meshes, which, then, increased the IPF in the pipe by 70% when the mesh size was 80 μm or less.

Zitieren

APA

LEE, Y. P., LEE, S. H., & YOO, H. (2010). REALIZATION OF HIGH IPF ICE SLURRY FOR DISTRICT COOLING. International Journal of Air-Conditioning and Refrigeration. https://doi.org/10.1142/s2010132510000149

Vancouver

LEE YP, LEE SH, YOO H. REALIZATION OF HIGH IPF ICE SLURRY FOR DISTRICT COOLING. International Journal of Air-Conditioning and Refrigeration. 2010. doi:10.1142/s2010132510000149

BibTeX
@article{LEE2010,
  author = {LEE, YOON PYO and LEE, SANG HOON and YOO, HOSEON},
  title = {REALIZATION OF HIGH IPF ICE SLURRY FOR DISTRICT COOLING},
  journal = {International Journal of Air-Conditioning and Refrigeration},
  year = {2010},
  doi = {10.1142/s2010132510000149}
}
Kostenlos starten →