EUVIMEDEUVIMED entdecken
Crossref

Bilevel Optimization of Sizing and Control Strategy of Hybrid Energy Storage System in Urban Rail Transit Considering Substation Operation Stability

Hongzhi Dong, Zhongbei Tian, Joseph W. Spencer, David Fletcher, Siavash Hajiabady

IEEE Transactions on Transportation Electrification · 2024-12 · 10 (4) · 10102-10114

DOI: 10.1109/tte.2024.3385821 ↗

Kurz gefasst

Fachartikel in der Zeitschrift IEEE Transactions on Transportation Electrification, 2024-12. Verfasst von Hongzhi Dong und 4 weiteren Autor:innen. Die Arbeit wurde bisher 26-mal zitiert (Crossref) und nennt 40 Literaturangaben. Gefördert von: EPSRC through the Connected and Coordinated Train Operation and Traction Power Supply Systems.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

The hybrid energy storage system (HESS), which consists of battery and ultracapacitor (UC), can efficiently reduce the substation energy cost from grid and achieve the peak-shaving function, due to its characteristics of high-power density and high-energy density. The sizing of HESS affects the operation cost of whole system. Besides, operation stability (such as substation peak power and voltage fluctuations) is rarely considered in urban railway transit (URT) when sizing optimization of HESS is considered. Thus, this research proposes a sizing and control strategy optimization of HESS in URT. First, the mathematic model of URT with HESS is established, which is used to simulate URT and HESS operation state by a power flow analysis method. Then, based on the proposed HESS control principle, a bilevel optimization of HESS in URT is proposed. The master level aims to optimize the rated capacity and power of HESS, reducing total operational cost. Then, the HESS control strategy is optimized at slave level, reducing substation peak power and voltage fluctuations of URT. The case study is conducted based on the data of Merseyrail line in Liverpool. A comparison is also conducted, which shows that the proposed method can reduce daily operation cost by 12.68% of the substation, while the grid energy cost is decreased by 57.26%.

Förderung

  • EPSRC through the Connected and Coordinated Train Operation and Traction Power Supply Systems

Zitieren

APA

Dong, H., Tian, Z., Spencer, J. W., Fletcher, D., & Hajiabady, S. (2024). Bilevel Optimization of Sizing and Control Strategy of Hybrid Energy Storage System in Urban Rail Transit Considering Substation Operation Stability. IEEE Transactions on Transportation Electrification, 10(4), 10102-10114. https://doi.org/10.1109/tte.2024.3385821

Vancouver

Dong H, Tian Z, Spencer JW, Fletcher D, Hajiabady S. Bilevel Optimization of Sizing and Control Strategy of Hybrid Energy Storage System in Urban Rail Transit Considering Substation Operation Stability. IEEE Transactions on Transportation Electrification. 2024;10(4):10102-10114. doi:10.1109/tte.2024.3385821

BibTeX
@article{Dong2024,
  author = {Dong, Hongzhi and Tian, Zhongbei and Spencer, Joseph W. and Fletcher, David and Hajiabady, Siavash},
  title = {Bilevel Optimization of Sizing and Control Strategy of Hybrid Energy Storage System in Urban Rail Transit Considering Substation Operation Stability},
  journal = {IEEE Transactions on Transportation Electrification},
  year = {2024},
  volume = {10},
  number = {4},
  pages = {10102--10114},
  doi = {10.1109/tte.2024.3385821}
}