Optimal VSG BESS Sizing for Improving Grid-Following Converter Stability Under Various Dispatch Scenarios and Grid Strengths
IEEE Transactions on Sustainable Energy · 2025-07 · 16 (3) · 2210-2223
DOI: 10.1109/tste.2025.3546294 ↗Kurz gefasst
Fachartikel in der Zeitschrift IEEE Transactions on Sustainable Energy, 2025-07. Verfasst von Yunda Xu und 2 weiteren Autor:innen. Die Arbeit wurde bisher 7-mal zitiert (Crossref) und nennt 29 Literaturangaben. Gefördert von: Queensland Government Department of Tourism, Innovation and Sport for the project: Enabling the Queensland Power System of the Future.
Abstract (Originalsprache)
As renewable energy integration increases, ensuring stability of Inverter-Based Resources (IBRs) in weak grids is crucial, as grid-following (GFL) converters often become unstable under such conditions. Integrating virtual synchronous generator (VSG) batteries has shown potential to improve GFL stability, but determining the optimal size of the VSG required for stability remains an open question. Existing research typically relies on small-signal or impedance models for stability analysis, which are only valid at a single operating point and do not consider the full range of operating conditions, including various dispatch scenarios and grid strengths. This paper addresses this gap by proposing a novel methodology to visualize the system's stable operating region, offering insights into stability boundaries across various real power and grid impedance variations. Additionally, it introduces an optimal VSG battery sizing strategy that accounts for these variations, ensuring stability while minimizing VSG capacity. The strategy's effectiveness is validated through comprehensive PSCAD simulations, demonstrating its reliability across a wide range of real power and grid impedance operating points.
Förderung
- Queensland Government Department of Tourism
- Innovation and Sport for the project: Enabling the Queensland Power System of the Future
Zitieren
APA
Xu, Y., Yan, R., & Saha, T. K. (2025). Optimal VSG BESS Sizing for Improving Grid-Following Converter Stability Under Various Dispatch Scenarios and Grid Strengths. IEEE Transactions on Sustainable Energy, 16(3), 2210-2223. https://doi.org/10.1109/tste.2025.3546294
Vancouver
Xu Y, Yan R, Saha TK. Optimal VSG BESS Sizing for Improving Grid-Following Converter Stability Under Various Dispatch Scenarios and Grid Strengths. IEEE Transactions on Sustainable Energy. 2025;16(3):2210-2223. doi:10.1109/tste.2025.3546294
BibTeX
@article{Xu2025,
author = {Xu, Yunda and Yan, Ruifeng and Saha, Tapan Kumar},
title = {Optimal VSG BESS Sizing for Improving Grid-Following Converter Stability Under Various Dispatch Scenarios and Grid Strengths},
journal = {IEEE Transactions on Sustainable Energy},
year = {2025},
volume = {16},
number = {3},
pages = {2210--2223},
doi = {10.1109/tste.2025.3546294}
}