A Cross-Line Successive Fault Detection of Distribution Network Based on Zero-Sequence Capacitance Variation
IEEE Transactions on Smart Grid · 2026-09 · 17 (5) · 3789-3801
DOI: 10.1109/tsg.2026.3687196 ↗Kurz gefasst
Fachartikel in der Zeitschrift IEEE Transactions on Smart Grid, 2026-09. Verfasst von Xinqian Wang und 7 weiteren Autor:innen. Die Arbeit wurde bisher 2-mal zitiert (Crossref) und nennt 24 Literaturangaben. Gefördert von: National Natural Science Foundation of China, State Grid Shaanxi Electric Power Company Ltd..
Abstract (Originalsprache)
In non-effectively grounded system, the rise in phase voltage during single-phase grounding (SPG) fault poses a significant threat to the system’s insulation integrity. The increasing cabling rate in distribution network has led to a rising proportion of cross-line double successive single-phase grounding (SSPG) faults triggered by initial fault. To address the challenges of weak characteristic and difficult detection of such successive fault, this paper proposes a SSPG detection method based on zero-sequence capacitance variation. First, the dynamic zero-sequence equivalent network during successive faults is simplified, and derive the zero-sequence current (ZSC) expressions for each feeder under both overdamped and underdamped conditions. Subsequently, the singular value decomposition-total least squares extended Prony algorithm is employed to fit the zero-sequence voltage (ZSV) and ZSC, enabling the calculation of zero-sequence capacitance for both initial and successive faults in the complex frequency domain. A detection criterion is then constructed using the variation of capacitance. Finally, digital simulations and recorded field data validate the correctness and feasibility of the theoretical analysis.
Förderung
- National Natural Science Foundation of China
- State Grid Shaanxi Electric Power Company Ltd.
Zitieren
APA
Wang, X., Wang, X., Wei, X., Zhang, F., Gao, J., Wang, Y., Gan, X., & Kheshti, M. (2026). A Cross-Line Successive Fault Detection of Distribution Network Based on Zero-Sequence Capacitance Variation. IEEE Transactions on Smart Grid, 17(5), 3789-3801. https://doi.org/10.1109/tsg.2026.3687196
Vancouver
Wang X, Wang X, Wei X, Zhang F, Gao J, Wang Y, et al. A Cross-Line Successive Fault Detection of Distribution Network Based on Zero-Sequence Capacitance Variation. IEEE Transactions on Smart Grid. 2026;17(5):3789-3801. doi:10.1109/tsg.2026.3687196
BibTeX
@article{Wang2026,
author = {Wang, Xinqian and Wang, Xiaowei and Wei, Xiangxiang and Zhang, Fan and Gao, Jie and Wang, Yizhao and Gan, Xinglin and Kheshti, Mostafa},
title = {A Cross-Line Successive Fault Detection of Distribution Network Based on Zero-Sequence Capacitance Variation},
journal = {IEEE Transactions on Smart Grid},
year = {2026},
volume = {17},
number = {5},
pages = {3789--3801},
doi = {10.1109/tsg.2026.3687196}
}