A Method for Identifying the Medium-Voltage Phase-to-Phase Short-Circuit Fault Section in Active Distribution Networks Based on the Equivalent Impedance Ratio of Low-Voltage Monitoring Nodes

Zhihua Zhang, Haojie Shi, Guang Li, Duhao Song, Yuxiao Xing, Bingyin Xu, Hongjie Wu

IEEE Transactions on Smart Grid · 2025-11 · 16 (6) · 4534-4548

DOI: 10.1109/tsg.2025.3596767 ↗

Kurz gefasst

Fachartikel in der Zeitschrift IEEE Transactions on Smart Grid, 2025-11. Verfasst von Zhihua Zhang und 6 weiteren Autor:innen. Die Arbeit wurde bisher 5-mal zitiert (Crossref) und nennt 36 Literaturangaben. Gefördert von: National Natural Science Foundation of China General Program: Research on the Mechanism of Energy Dynamic Balance and Reverse Power Protection Strategy in AC/D….

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Distributed generation (DG) integration into distribution networks brings new challenges to fault location in medium-voltage (MV) distribution networks. The popular smart fusion terminals on the low-voltage (LV) transformer area provide new data support for fault location in distribution networks. In this study, for phase-to-phase short-circuit faults in distribution networks, first, the mapping relationship between LV line voltage at each LV monitoring node and MV phase voltage sequence components is analyzed, the ratio of the impedances from each monitoring node and the short-circuit point to the system is defined as the equivalent impedance ratio, and a method for inversely calculating the equivalent impedance ratio using LV line voltage amplitude is proposed. Second, a method for identifying the phase-to-phase short-circuit fault section of MV distribution networks based on the impedance ratio change characteristics is proposed. Next, the analysis model for phase-to-phase short-circuit faults in systems containing DG is established, and the influence of its output characteristics on this method is analyzed. Finally, the simulating results show that this method is not affected by factors such as access locations and capacity of DG, simultaneous faults, transformer connections, fault resistance, transformer transmission error, measurement error, asynchronous data and load size and has a certain degree of robustness.

Förderung

  • National Natural Science Foundation of China General Program: Research on the Mechanism of Energy Dynamic Balance and Reverse Power Protection Strategy in AC/D…

Zitieren

APA

Zhang, Z., Shi, H., Li, G., Song, D., Xing, Y., Xu, B., & Wu, H. (2025). A Method for Identifying the Medium-Voltage Phase-to-Phase Short-Circuit Fault Section in Active Distribution Networks Based on the Equivalent Impedance Ratio of Low-Voltage Monitoring Nodes. IEEE Transactions on Smart Grid, 16(6), 4534-4548. https://doi.org/10.1109/tsg.2025.3596767

Vancouver

Zhang Z, Shi H, Li G, Song D, Xing Y, Xu B, et al. A Method for Identifying the Medium-Voltage Phase-to-Phase Short-Circuit Fault Section in Active Distribution Networks Based on the Equivalent Impedance Ratio of Low-Voltage Monitoring Nodes. IEEE Transactions on Smart Grid. 2025;16(6):4534-4548. doi:10.1109/tsg.2025.3596767

BibTeX
@article{Zhang2025,
  author = {Zhang, Zhihua and Shi, Haojie and Li, Guang and Song, Duhao and Xing, Yuxiao and Xu, Bingyin and Wu, Hongjie},
  title = {A Method for Identifying the Medium-Voltage Phase-to-Phase Short-Circuit Fault Section in Active Distribution Networks Based on the Equivalent Impedance Ratio of Low-Voltage Monitoring Nodes},
  journal = {IEEE Transactions on Smart Grid},
  year = {2025},
  volume = {16},
  number = {6},
  pages = {4534--4548},
  doi = {10.1109/tsg.2025.3596767}
}
Kostenlos starten →