EUVIMEDEUVIMED entdecken
Crossref

Reduced-Scale Test Method for Dynamic Responses of Bundle Conductor Line Following Ice-Shedding

Bo Yan, Xinrui Zhou, Wei Zong, Huachao Deng, Jin Li, Ming Hua, Xiaoqian Ma

IEEE Transactions on Power Delivery · 2026-10 · 41 (5) · 2584-2595

DOI: 10.1109/tpwrd.2026.3697446 ↗

Kurz gefasst

Fachartikel in der Zeitschrift IEEE Transactions on Power Delivery, 2026-10. Verfasst von Bo Yan und 6 weiteren Autor:innen. Die Arbeit wurde bisher 1-mal zitiert (Crossref) und nennt 26 Literaturangaben. Gefördert von: Science and Technology Project of State Grid Corporation of China.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

A reduced-scale test method for dynamic responses of bundle conductor line following ice-shedding is proposed. In this method, hollow cylindrical electromagnets are used to absorb and release mass blocks modelling ice on and ice-shedding from sub-conductors, multiple cameras are utilized to capture the vertical, transverse and torsional vibrations, tension sensors to measure tensions in all sub-conductors, and three-component force sensors to measure the reaction force at hanging points. Without simplifying the bundle conductor line into a single one which was employed in previous works, the proposed reduced-scale model can satisfy the similarities of bending and torsion stiffness at the same time, model the torsional vibration induced by ice-shedding from sub-conductors, and record tension in each sub-conductor. Reduced-scale test platform for a twin-bundle conductor line was established and utilized to study the dynamic characteristics of the twin-bundle conductor line following partial, unzipping and asynchronous ice-shedding from sub-conductors. The method can be extended to investigate dynamic characteristics of bundle conductor lines following any pattern of ice-shedding.

Förderung

  • Science and Technology Project of State Grid Corporation of China

Zitieren

APA

Yan, B., Zhou, X., Zong, W., Deng, H., Li, J., Hua, M., & Ma, X. (2026). Reduced-Scale Test Method for Dynamic Responses of Bundle Conductor Line Following Ice-Shedding. IEEE Transactions on Power Delivery, 41(5), 2584-2595. https://doi.org/10.1109/tpwrd.2026.3697446

Vancouver

Yan B, Zhou X, Zong W, Deng H, Li J, Hua M, et al. Reduced-Scale Test Method for Dynamic Responses of Bundle Conductor Line Following Ice-Shedding. IEEE Transactions on Power Delivery. 2026;41(5):2584-2595. doi:10.1109/tpwrd.2026.3697446

BibTeX
@article{Yan2026,
  author = {Yan, Bo and Zhou, Xinrui and Zong, Wei and Deng, Huachao and Li, Jin and Hua, Ming and Ma, Xiaoqian},
  title = {Reduced-Scale Test Method for Dynamic Responses of Bundle Conductor Line Following Ice-Shedding},
  journal = {IEEE Transactions on Power Delivery},
  year = {2026},
  volume = {41},
  number = {5},
  pages = {2584--2595},
  doi = {10.1109/tpwrd.2026.3697446}
}
Kostenlos starten →