Condition Monitoring of Cap and Pin Insulator String by Electric Field Mapping Using Electro-Optical Probes With FEA Model Validation
IEEE Transactions on Power Delivery · 2026-02 · 41 (1) · 105-114
DOI: 10.1109/tpwrd.2025.3624014 ↗Kurz gefasst
Fachartikel in der Zeitschrift IEEE Transactions on Power Delivery, 2026-02. Verfasst von Fang Liu und 12 weiteren Autor:innen. Die Arbeit wurde bisher 7-mal zitiert (Crossref) und nennt 27 Literaturangaben.
Abstract (Originalsprache)
Cap and pin insulators are widely used in electricity transmission towers in power systems and are one of their key functional elements. This paper reports on a successful application of using electric field as an index to detect and locate shorted insulator units in a cap and pin string. Electro-optical (EO) probes were used to measure the electrical field, and a six-axis robotic arm, holding the probes, enabled electrical field mapping at different spatial locations. The electric field distribution was first plotted according to the measurements performed by EO probes travelling along straight lines parallel to the string, and then a closer examination between insulator sheds was conducted to evaluate the possibility of higher accuracy locating of shorted insulator units. The measured changes in electric field distribution were compared with predictions from corresponding electrostatic finite element analysis (FEA) models, confirming the ability of locating shorted units in the string based on observation of the field spatial distribution change. The electric field monitoring system was also further developed to achieve operator-free and automated data acquisition and recording. The reported methodology exhibits promising potential in live condition monitoring of insulator strings in high voltage (HV) towers.
Zitieren
APA
Liu, F., Lopez, E., Afia, R., West, A., McDonald, H., Peesapati, V., Djurović, S., Cotton, I., Kabbabe, K., Mbisike, S., Stewart, D., Gaborit, G., & Duvillaret, L. (2026). Condition Monitoring of Cap and Pin Insulator String by Electric Field Mapping Using Electro-Optical Probes With FEA Model Validation. IEEE Transactions on Power Delivery, 41(1), 105-114. https://doi.org/10.1109/tpwrd.2025.3624014
Vancouver
Liu F, Lopez E, Afia R, West A, McDonald H, Peesapati V, et al. Condition Monitoring of Cap and Pin Insulator String by Electric Field Mapping Using Electro-Optical Probes With FEA Model Validation. IEEE Transactions on Power Delivery. 2026;41(1):105-114. doi:10.1109/tpwrd.2025.3624014
BibTeX
@article{Liu2026,
author = {Liu, Fang and Lopez, Erwin and Afia, Ramy and West, Andrew and McDonald, Harry and Peesapati, Vidyadhar and Djurović, Siniša and Cotton, Ian and Kabbabe, Khristopher and Mbisike, Stephen and Stewart, Damon and Gaborit, Gwenaël and Duvillaret, Lionel},
title = {Condition Monitoring of Cap and Pin Insulator String by Electric Field Mapping Using Electro-Optical Probes With FEA Model Validation},
journal = {IEEE Transactions on Power Delivery},
year = {2026},
volume = {41},
number = {1},
pages = {105--114},
doi = {10.1109/tpwrd.2025.3624014}
}