Traveling Wave Differential Protection Technology and Its Application in Ultra-Long-Distance UHVDC Transmission Line
IEEE Transactions on Power Delivery · 2025-04 · 40 (2) · 1078-1088
DOI: 10.1109/tpwrd.2025.3536181 ↗Kurz gefasst
Fachartikel in der Zeitschrift IEEE Transactions on Power Delivery, 2025-04. Verfasst von Xinzhou Dong und 14 weiteren Autor:innen. Die Arbeit wurde bisher 14-mal zitiert (Crossref) und nennt 36 Literaturangaben.
Abstract (Originalsprache)
Traveling wave differential protection (TWDP) is based on the traveling wave (TW) propagation characteristics of the physical transmission line and therefore holds unique advantages in the protection of long-distance transmission lines. This paper proposes a practical time-domain TWDP scheme specifically designed for high-voltage direct-current (HVDC) lines and provides both theoretical analysis and field validation. A TWDP device, named TP-03, was developed and underwent laboratory testing. The developed protection device 1) can stay valid under a maximum fault impedance of up to 1000 $\Omega$ under the rated $\pm$ 1100 kV voltage level; 2) has an operation time of less than 30 ms even with a communication delay of 20 ms. In October 2020, TP-03 devices were first deployed on the Changji-Guquan UHVDC transmission project, which is the highest voltage ( $\pm$ 1100 kV), longest distance (3284 km), and largest capacity (rated 12100 MW) transmission project in the world. During its operation, the devices functioned correctly in several internal faults and external disturbance events. This work represents the first field validation of HVDC TWDP and bridges the gap between theoretical research and real-world applications. It confirms that TWDP can serve as the main protection for ultra-long-distance HVDC lines, setting a benchmark for future projects.
Zitieren
APA
Dong, X., Wang, H., Chen, B., Jin, B., Li, X., Dong, Q., Shi, S., Wang, B., Lv, P., Qian, G., Chen, F., Fan, Z., Li, B., Xie, M., & Feng, X. (2025). Traveling Wave Differential Protection Technology and Its Application in Ultra-Long-Distance UHVDC Transmission Line. IEEE Transactions on Power Delivery, 40(2), 1078-1088. https://doi.org/10.1109/tpwrd.2025.3536181
Vancouver
Dong X, Wang H, Chen B, Jin B, Li X, Dong Q, et al. Traveling Wave Differential Protection Technology and Its Application in Ultra-Long-Distance UHVDC Transmission Line. IEEE Transactions on Power Delivery. 2025;40(2):1078-1088. doi:10.1109/tpwrd.2025.3536181
BibTeX
@article{Dong2025,
author = {Dong, Xinzhou and Wang, Haozong and Chen, Binshu and Jin, Boliang and Li, Xinyuan and Dong, Qihuan and Shi, Shenxing and Wang, Bin and Lv, Pengfei and Qian, Guoming and Chen, Fufeng and Fan, Zhanfeng and Li, Baowei and Xie, Min and Feng, Xiaoping},
title = {Traveling Wave Differential Protection Technology and Its Application in Ultra-Long-Distance UHVDC Transmission Line},
journal = {IEEE Transactions on Power Delivery},
year = {2025},
volume = {40},
number = {2},
pages = {1078--1088},
doi = {10.1109/tpwrd.2025.3536181}
}