Protection of Line Faults in HVDC Grids Through Convexity Detection in Backward Traveling Wave Voltages
IEEE Transactions on Power Delivery · 2023-10 · 38 (5) · 3660-3676
DOI: 10.1109/tpwrd.2023.3286863 ↗Kurz gefasst
Fachartikel in der Zeitschrift IEEE Transactions on Power Delivery, 2023-10. Verfasst von Ting Wang und 5 weiteren Autor:innen. Die Arbeit wurde bisher 18-mal zitiert (Crossref) und nennt 50 Literaturangaben. Gefördert von: National Natural Science Foundation of China.
Abstract (Originalsprache)
Short-circuit faults in high-voltage DC (HVDC) grids must be timely isolated. Conventional fault isolation schemes for HVDC grids typically rely on numerical simulations or analytical calculations for threshold setting, which complicate engineering implementation. To solve this issue, this article first introduces the convex point of backward traveling wave (BTW) voltage as the reference for the faulty line isolation in HVDC grids, which is interpreted as the singular feature in the second derivative (SD) of BTW voltage. The singularity in the SD of BTW voltage is independent of system or fault parameters, having good generality in HVDC grids. Through recognizing the unique pattern in the wavelet transform modulus maxima of the singular feature, the proposed protection method can identify faulty lines in HVDC grids in the initial phase of faults. Numerical studies carried out with PSCAD/EMTDC and MATLAB/Simulink demonstrate the effectiveness, robustness and applicability of the proposed method in detecting and isolating various single- and double-pole faults in HVDC grids.
Förderung
- National Natural Science Foundation of China
Zitieren
APA
Wang, T., Yu, Z., Xie, F., Hao, Z., Monti, A., & Ponci, F. (2023). Protection of Line Faults in HVDC Grids Through Convexity Detection in Backward Traveling Wave Voltages. IEEE Transactions on Power Delivery, 38(5), 3660-3676. https://doi.org/10.1109/tpwrd.2023.3286863
Vancouver
Wang T, Yu Z, Xie F, Hao Z, Monti A, Ponci F. Protection of Line Faults in HVDC Grids Through Convexity Detection in Backward Traveling Wave Voltages. IEEE Transactions on Power Delivery. 2023;38(5):3660-3676. doi:10.1109/tpwrd.2023.3286863
BibTeX
@article{Wang2023,
author = {Wang, Ting and Yu, Zexue and Xie, Fan and Hao, Zhiguo and Monti, Antonello and Ponci, Ferdinanda},
title = {Protection of Line Faults in HVDC Grids Through Convexity Detection in Backward Traveling Wave Voltages},
journal = {IEEE Transactions on Power Delivery},
year = {2023},
volume = {38},
number = {5},
pages = {3660--3676},
doi = {10.1109/tpwrd.2023.3286863}
}
EUVIMED