Optimal Weighted Distributional Monitoring for Intermittent Fault Detection in Stationary Power Systems

Ke Sheng, Min Wang, Feiyang Cheng, Zhen Liu, Chengcheng Wang

IEEE Transactions on Instrumentation and Measurement · 2026 · 75 · 3517011-3517011

DOI: 10.1109/tim.2026.3704276 ↗

Kurz gefasst

Fachartikel in der Zeitschrift IEEE Transactions on Instrumentation and Measurement, 2026. Verfasst von Ke Sheng und 4 weiteren Autor:innen. Die Arbeit nennt 35 Literaturangaben. Gefördert von: National Natural Science Foundation of China, Key Laboratory of Equipment Data Security and Guarantee Technology, Ministry of Education.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Intermittent faults (IFs) in power systems pose significant threats to operational reliability. Owing to the transient, stochastic, and covert characteristics, these faults are exceptionally difficult to detect. Although the weighted moving average technique enhances detection sensitivity, a critical research gap remains: their performance is fundamentally limited by the primarily first-order monitoring hypothesis analysis. Since practical IFs induce severe variations in the process covariance structure and distort the overall data distribution, these first-order-based methods remain blind to higher order effects, resulting in high rates of missed detections. To bridge this gap, this article introduces a novel optimal weighted distributional monitoring statistics (OWDMS) method. The method effectively integrates two key elements: 1) a monitoring strategy for the complete data distribution to capture complex system states and 2) an optimal moving average weighted technique to enhance sensitivity to hidden IF characteristics. The optimization of the proposed method is rigorously derived by maximizing the expected deviation of the monitoring statistic and the maximum likelihood principle. Ultimately, a three-phase full-bridge inverter system experimental platform demonstrates its exceptional performance, yielding a fault detection rate (FDR) over 17 % higher than that of existing methods.

Förderung

  • National Natural Science Foundation of China
  • Key Laboratory of Equipment Data Security and Guarantee Technology, Ministry of Education

Zitieren

APA

Sheng, K., Wang, M., Cheng, F., Liu, Z., & Wang, C. (2026). Optimal Weighted Distributional Monitoring for Intermittent Fault Detection in Stationary Power Systems. IEEE Transactions on Instrumentation and Measurement, 75, 3517011-3517011. https://doi.org/10.1109/tim.2026.3704276

Vancouver

Sheng K, Wang M, Cheng F, Liu Z, Wang C. Optimal Weighted Distributional Monitoring for Intermittent Fault Detection in Stationary Power Systems. IEEE Transactions on Instrumentation and Measurement. 2026;75:3517011-3517011. doi:10.1109/tim.2026.3704276

BibTeX
@article{Sheng2026,
  author = {Sheng, Ke and Wang, Min and Cheng, Feiyang and Liu, Zhen and Wang, Chengcheng},
  title = {Optimal Weighted Distributional Monitoring for Intermittent Fault Detection in Stationary Power Systems},
  journal = {IEEE Transactions on Instrumentation and Measurement},
  year = {2026},
  volume = {75},
  pages = {3517011--3517011},
  doi = {10.1109/tim.2026.3704276}
}
Kostenlos starten →