Early Warning of Arcing Interturn Short-Circuit Faults in Transformer Windings Using Broadband Acoustic Emission

Yizhuo Hu, Ji Chen, Qiang Zeng, Shuhua Li, Qian Wu, Chongxing Zhang, Ming Dong, Ming Ren

IEEE Transactions on Instrumentation and Measurement · 2026 · 75 · 9005814-9005814

DOI: 10.1109/tim.2026.3704214 ↗

Kurz gefasst

Fachartikel in der Zeitschrift IEEE Transactions on Instrumentation and Measurement, 2026. Verfasst von Yizhuo Hu und 7 weiteren Autor:innen. Die Arbeit nennt 40 Literaturangaben. Gefördert von: National Key Research and Development Program of China.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Arcing interturn short-circuit (ITSC) faults are difficult to detect at an early stage because the associated terminal electrical variations are weak and can be masked by the transformer winding network. This article investigates broadband acoustic emission (AE) characteristics for early warning of arcing ITSC faults. A simplified multiturn winding model is developed based on the interturn potential distribution of high-voltage transformer windings, and controlled experiments are conducted to emulate the progression from single-turn breakdown (BD) to multiturn arcing (MTA) with synchronized electrical, optical, and AE measurements. The simplified model is described using an impedance-division and arc-conductance formulation to clarify the voltage redistribution and cascading BD mechanism. Experimental results show that interturn arcs generate AE signals over the kHz–MHz range, which can be decomposed into low-frequency narrowband (LF-NB), middle-frequency narrowband (MF-NB), and high-frequency broadband (HF-BB) components. Statistical analysis of 22 MTA tests indicates that the AE energy distribution shifts from low-/MF-NB dominance in the single-turn stage to HF-BB dominance in the multiturn stage. Based on these physically interpretable features, a graded early-warning strategy is proposed, with the Level-II criterion constructed from statistically determined AE band-ratio thresholds and preliminarily checked using a prototype-transformer-model test. The results demonstrate the potential of broadband AE features for early warning of arcing ITSC faults in oil-immersed transformer windings.

Förderung

  • National Key Research and Development Program of China

Zitieren

APA

Hu, Y., Chen, J., Zeng, Q., Li, S., Wu, Q., Zhang, C., Dong, M., & Ren, M. (2026). Early Warning of Arcing Interturn Short-Circuit Faults in Transformer Windings Using Broadband Acoustic Emission. IEEE Transactions on Instrumentation and Measurement, 75, 9005814-9005814. https://doi.org/10.1109/tim.2026.3704214

Vancouver

Hu Y, Chen J, Zeng Q, Li S, Wu Q, Zhang C, et al. Early Warning of Arcing Interturn Short-Circuit Faults in Transformer Windings Using Broadband Acoustic Emission. IEEE Transactions on Instrumentation and Measurement. 2026;75:9005814-9005814. doi:10.1109/tim.2026.3704214

BibTeX
@article{Hu2026,
  author = {Hu, Yizhuo and Chen, Ji and Zeng, Qiang and Li, Shuhua and Wu, Qian and Zhang, Chongxing and Dong, Ming and Ren, Ming},
  title = {Early Warning of Arcing Interturn Short-Circuit Faults in Transformer Windings Using Broadband Acoustic Emission},
  journal = {IEEE Transactions on Instrumentation and Measurement},
  year = {2026},
  volume = {75},
  pages = {9005814--9005814},
  doi = {10.1109/tim.2026.3704214}
}
Kostenlos starten →