False Alarm Reduction in DC Series Arc Detection Using Asymmetrical Gini Impurity
IEEE Transactions on Instrumentation and Measurement · 2025 · 74 · 1-12
DOI: 10.1109/tim.2025.3635319 ↗Kurz gefasst
Fachartikel in der Zeitschrift IEEE Transactions on Instrumentation and Measurement, 2025. Verfasst von Weiyu You und 6 weiteren Autor:innen. Die Arbeit wurde bisher 3-mal zitiert (Crossref) und nennt 37 Literaturangaben. Gefördert von: National Major Science and Technology Project for Intelligent Manufacturing Systems and Robotics of China, China National Research and Development Key Research Program.
Abstract (Originalsprache)
The power generation and loads of photovoltaic (PV) systems are inherently intermittent, periodic, and stochastic, resulting in nonstationary dynamic fluctuations in line currents. These dynamics have overlapping spectral features with dc series arcs, which increases the likelihood of false alarms and reduces the accuracy of arc detection. To address this problem, a dc series arc diagnosis method based on asymmetrical Gini impurity is proposed to reduce the false alarm rate (FAR) while ensuring accuracy. First, arc fault current data under various operating conditions are collected through experiments. To mitigate the impact of periodic fluctuations and enhance the detection of transient current changes, a multistep differential processing method is employed. Second, the time- and frequency-domain features of arc faults are extracted from the differential signal to construct a high-dimensional feature vector. To reduce redundant features, the clustering algorithm is applied to identify and group features demonstrating analogous classification performance, and the asymmetrical Gini impurity (AGI) is introduced to analyze feature significance. Finally, a random forest (RF) model based on AGI is utilized for dc series arc diagnosis. The experimental results demonstrate that the proposed method not only achieves high diagnosis accuracy and effectively reduces the FAR, but also completes fault detection within 60 ms.
Förderung
- National Major Science and Technology Project for Intelligent Manufacturing Systems and Robotics of China
- China National Research and Development Key Research Program
Zitieren
APA
You, W., Yang, G., Ju, C., Wang, L., Chen, Z., Wang, Y., & Xu, P. (2025). False Alarm Reduction in DC Series Arc Detection Using Asymmetrical Gini Impurity. IEEE Transactions on Instrumentation and Measurement, 74, 1-12. https://doi.org/10.1109/tim.2025.3635319
Vancouver
You W, Yang G, Ju C, Wang L, Chen Z, Wang Y, et al. False Alarm Reduction in DC Series Arc Detection Using Asymmetrical Gini Impurity. IEEE Transactions on Instrumentation and Measurement. 2025;74:1-12. doi:10.1109/tim.2025.3635319
BibTeX
@article{You2025,
author = {You, Weiyu and Yang, Genke and Ju, Changjiang and Wang, Lin and Chen, Zekai and Wang, Yiming and Xu, Po},
title = {False Alarm Reduction in DC Series Arc Detection Using Asymmetrical Gini Impurity},
journal = {IEEE Transactions on Instrumentation and Measurement},
year = {2025},
volume = {74},
pages = {1--12},
doi = {10.1109/tim.2025.3635319}
}
EUVIMED