AC Loss Measurement for 10 kV/1 Mvar Toroidal Air-Core Superconducting Reactor Based on Boil-off Method
IEEE Transactions on Applied Superconductivity · 2026-08 · 36 (5) · 1-6
DOI: 10.1109/tasc.2026.3674123 ↗Kurz gefasst
Fachartikel in der Zeitschrift IEEE Transactions on Applied Superconductivity, 2026-08. Verfasst von Shuhao Peng und 9 weiteren Autor:innen. Die Arbeit nennt 28 Literaturangaben. Gefördert von: State Grid Corporation of China Science and Technology Project.
Abstract (Originalsprache)
Installing shunt reactors is currently an effective solution for the problem of local reactive power absorption. However, conventional reactors have a large footprint and high noise emissions, making them difficult to deploy in space-constrained substations in urban areas. High-temperature superconducting shunt reactors with a toroidal air-core topology effectively improve the power density of reactive power compensation, while reducing energy loss, spatial magnetic flux leakage, and noise pollution. This enables more compact, lightweight, flexible, and reliable reactive power compensation devices. Nevertheless, the AC loss generated by superconducting reactors during operation is difficult to measure via conventional electrical methods, due to the high inductance of the reactor coils. In this paper, a calibration-free method is adopted to derive the relationship between liquid nitrogen evaporation flow rate and AC loss, which is applied to measure the AC loss of the proposed toroidal air-core superconducting reactor. The measurement results show good agreement with simulation data, verifying the reliability of the proposed method. The 10 kV/1 MVar reactor exhibits a low AC loss of 515 W at rated operating conditions, with a total system loss of 736.03 W. This work provides a valuable reference for the loss testing and performance evaluation of large-scale superconducting magnets.
Förderung
- State Grid Corporation of China Science and Technology Project
Zitieren
APA
Peng, S., Sheng, J., Xu, Q., Li, H., Yang, Z., Zhou, X., Zhao, R., Zhang, X., Yang, K., & Jin, Z. (2026). AC Loss Measurement for 10 kV/1 Mvar Toroidal Air-Core Superconducting Reactor Based on Boil-off Method. IEEE Transactions on Applied Superconductivity, 36(5), 1-6. https://doi.org/10.1109/tasc.2026.3674123
Vancouver
Peng S, Sheng J, Xu Q, Li H, Yang Z, Zhou X, et al. AC Loss Measurement for 10 kV/1 Mvar Toroidal Air-Core Superconducting Reactor Based on Boil-off Method. IEEE Transactions on Applied Superconductivity. 2026;36(5):1-6. doi:10.1109/tasc.2026.3674123
BibTeX
@article{Peng2026,
author = {Peng, Shuhao and Sheng, Jie and Xu, Qingchuan and Li, Honglei and Yang, Zhixing and Zhou, Xuan and Zhao, Ruiming and Zhang, Xiangde and Yang, Kaiyue and Jin, Zhijian},
title = {AC Loss Measurement for 10 kV/1 Mvar Toroidal Air-Core Superconducting Reactor Based on Boil-off Method},
journal = {IEEE Transactions on Applied Superconductivity},
year = {2026},
volume = {36},
number = {5},
pages = {1--6},
doi = {10.1109/tasc.2026.3674123}
}
EUVIMED