Assessment of Power Quality in an Industrial Facility: A Case Study at DESY Hamburg
IEEE Open Journal of Instrumentation and Measurement · 2025 · 4 · 1-11
DOI: 10.1109/ojim.2025.3629874 ↗Kurz gefasst
Fachartikel in der Zeitschrift IEEE Open Journal of Instrumentation and Measurement, 2025. Verfasst von Sulaiman Elrajoubi und 4 weiteren Autor:innen. Die Arbeit wurde bisher 6-mal zitiert (Crossref) und nennt 27 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Deutsches Elektronen-Synchrotron (DESY) through the Project Harmonic Stability in Power Electronic-Based Power Systems.
Abstract (Originalsprache)
This article presents a comprehensive assessment of power quality (PQ) disturbances in the industrial power network of the Deutsches Elektronen-Synchrotron (DESY), a leading research facility for particle physics. The study leverages high-resolution measurements (7-days) from Fluke 435 Series II and long-term monitoring data (6-months) from Janitza UMG 512 analyzers to characterize PQ issues. Measurement data were collected from various substations and Points of Common Coupling (PCC) to evaluate harmonics, voltage fluctuations, flicker, and transient events. The high-resolution data (sampled at 500 ms) revealed voltage deviations of up to ±4%, current unbalance exceeding ±10%, and flicker spikes reaching 0.63 Pst, all attributed to nonlinear load dynamics and switching events. In total, 17 voltage swell events and 12 dips were recorded, along with 6 transient disturbances linked to PETRA’s 12-pulse converter operations. Also, voltage and current total harmonic distortion (THD) levels peaked at 3.6% and 7.5%, respectively, breaching IEEE 519 thresholds under dynamic loading. These findings highlight the necessity of coordinated PQ monitoring strategies and support the development of predictive, data-driven PQ management frameworks tailored to mission-critical industrial networks.
Förderung
- Deutsches Elektronen-Synchrotron (DESY) through the Project Harmonic Stability in Power Electronic-Based Power Systems
Zitieren
APA
Elrajoubi, S., Faesing, M., Eckoldt, H., Ponci, F., & Monti, A. (2025). Assessment of Power Quality in an Industrial Facility: A Case Study at DESY Hamburg. IEEE Open Journal of Instrumentation and Measurement, 4, 1-11. https://doi.org/10.1109/ojim.2025.3629874
Vancouver
Elrajoubi S, Faesing M, Eckoldt H, Ponci F, Monti A. Assessment of Power Quality in an Industrial Facility: A Case Study at DESY Hamburg. IEEE Open Journal of Instrumentation and Measurement. 2025;4:1-11. doi:10.1109/ojim.2025.3629874
BibTeX
@article{Elrajoubi2025,
author = {Elrajoubi, Sulaiman and Faesing, Markus and Eckoldt, Hans-Jörg and Ponci, Ferdinanda and Monti, Antonello},
title = {Assessment of Power Quality in an Industrial Facility: A Case Study at DESY Hamburg},
journal = {IEEE Open Journal of Instrumentation and Measurement},
year = {2025},
volume = {4},
pages = {1--11},
doi = {10.1109/ojim.2025.3629874}
}
EUVIMED