Switchgear Fault Diagnosis Method Based on RFID Sensor Tag and DBN-WOA-ELM

Bing Li, Huimin Yang, Baiqiang Yin, Shudong Wang, Zhongxin Xie, Tianyun Hu, Lei Zuo

IEEE Sensors Journal · 15.07.2026 · 26 (14) · 21603-21613

DOI: 10.1109/jsen.2026.3702300 ↗

Kurz gefasst

Fachartikel in der Zeitschrift IEEE Sensors Journal, erschienen am 15.07.2026. Verfasst von Bing Li und 6 weiteren Autor:innen. Die Arbeit nennt 30 Literaturangaben. Gefördert von: Electric Power Science Research Institute, State Grid Anhui Electric Power.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

As a core device responsible for power interruption and electrical protection, switchgear requires accurate and efficient fault diagnosis. To improve the diagnosis accuracy, this article proposes a novel fault diagnosis method based on deep belief network (DBN)–whale optimization algorithm (WOA)–extreme learning machine (ELM). First, wireless radio frequency identification (RFID) sensor tags are designed to collect temperature and humidity signals from switchgear. This approach offers the advantages of low power consumption and high real-time performance. Subsequently, a DBN is employed to extract features from the measured signals. The Softmax classifier in the traditional DBN is replaced with an ELM to further analyze the correlation between feature values and fault types, thereby enhancing the convergence speed of the model. Furthermore, the WOA is utilized to optimize the input weights and hidden layer biases of the ELM model, improving both the accuracy and stability of the diagnostic results. Finally, the features extracted by the DBN are fed into the optimized ELM for fault identification. Experimental results show that the proposed DBN–WOA–ELM method achieves a fault diagnosis accuracy of 99.21%, which is approximately 1.25%–3.7% higher than the other four fault diagnosis methods, while also reducing the testing time by approximately 16%–56%. The developed RFID sensor tag operates in a passive mode, with an average power consumption of approximately $115~\mu $ W. It achieves a maximum communication distance of 9.4 m and a minimum system-level sensitivity of −17 dBm, demonstrating its suitability for low-power online monitoring applications.

Förderung

  • Electric Power Science Research Institute, State Grid Anhui Electric Power

Zitieren

APA

Li, B., Yang, H., Yin, B., Wang, S., Xie, Z., Hu, T., & Zuo, L. (2026). Switchgear Fault Diagnosis Method Based on RFID Sensor Tag and DBN-WOA-ELM. IEEE Sensors Journal, 26(14), 21603-21613. https://doi.org/10.1109/jsen.2026.3702300

Vancouver

Li B, Yang H, Yin B, Wang S, Xie Z, Hu T, et al. Switchgear Fault Diagnosis Method Based on RFID Sensor Tag and DBN-WOA-ELM. IEEE Sensors Journal. 2026;26(14):21603-21613. doi:10.1109/jsen.2026.3702300

BibTeX
@article{Li2026,
  author = {Li, Bing and Yang, Huimin and Yin, Baiqiang and Wang, Shudong and Xie, Zhongxin and Hu, Tianyun and Zuo, Lei},
  title = {Switchgear Fault Diagnosis Method Based on RFID Sensor Tag and DBN-WOA-ELM},
  journal = {IEEE Sensors Journal},
  year = {2026},
  volume = {26},
  number = {14},
  pages = {21603--21613},
  doi = {10.1109/jsen.2026.3702300}
}
Kostenlos starten →