EUVIMEDEUVIMED entdecken
Crossref

Dual-Stage Optimized SSTDR for High Accuracy Online Cable Fault Localization

Hongzhen Chen, Li Wang, Shanshui Yang, Hao Xu, Yunxuan Li

IEEE Sensors Journal · 15.05.2026 · 26 (10) · 16297-16310

DOI: 10.1109/jsen.2026.3681182 ↗

Kurz gefasst

Fachartikel in der Zeitschrift IEEE Sensors Journal, erschienen am 15.05.2026. Verfasst von Hongzhen Chen und 4 weiteren Autor:innen. Gefördert von: National Natural Science Foundation of China.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

The cable fault online detection and localization technology based on spread spectrum time domain reflectometry (SSTDR) can effectively enhance system operation reliability and continuity while reducing operation and maintenance costs. It is of great significance for the protection of key systems such as electric power, communication, and transportation. However, in practical engineering applications, the reduced localization accuracy for detecting long-distance faults limits its applicability. Based on the analysis of the impact mechanisms of signal attenuation, hardware sampling rate, and noise interference on localization accuracy, this article proposes a dual-stage optimized SSTDR method to enhance localization accuracy over long distances. The method first performs cubic spline interpolation resampling on the incident and reflected signals in the time domain, then conducts cross correlation between them, and finally employs the square-weighted centroid algorithm to correct the peak position in the cross correlation result. This method requires no modifications to the hardware platform and features low computational complexity, offering high engineering applicability. Experimental validation demonstrates that this approach effectively improves the localization accuracy of SSTDR. Within the test range of 400–3000 m, the average localization error is reduced to merely 14.96% of that achieved by traditional SSTDR. Furthermore, the dispersion of the localization error distribution is significantly reduced, indicating superior stability compared to conventional SSTDR.

Förderung

  • National Natural Science Foundation of China

Zitieren

APA

Chen, H., Wang, L., Yang, S., Xu, H., & Li, Y. (2026). Dual-Stage Optimized SSTDR for High Accuracy Online Cable Fault Localization. IEEE Sensors Journal, 26(10), 16297-16310. https://doi.org/10.1109/jsen.2026.3681182

Vancouver

Chen H, Wang L, Yang S, Xu H, Li Y. Dual-Stage Optimized SSTDR for High Accuracy Online Cable Fault Localization. IEEE Sensors Journal. 2026;26(10):16297-16310. doi:10.1109/jsen.2026.3681182

BibTeX
@article{Chen2026,
  author = {Chen, Hongzhen and Wang, Li and Yang, Shanshui and Xu, Hao and Li, Yunxuan},
  title = {Dual-Stage Optimized SSTDR for High Accuracy Online Cable Fault Localization},
  journal = {IEEE Sensors Journal},
  year = {2026},
  volume = {26},
  number = {10},
  pages = {16297--16310},
  doi = {10.1109/jsen.2026.3681182}
}
Kostenlos starten →