Dynamic Voltage Restorer With Integration of Least Mean Square and Optimal Type-2 Fuzzy

Prashant Kumar, Sabha Raj Arya, Papia Ray

IEEE Journal of Emerging and Selected Topics in Power Electronics · 2025-10 · 13 (5) · 6253-6262

DOI: 10.1109/jestpe.2025.3572004 ↗

Kurz gefasst

Fachartikel in der Zeitschrift IEEE Journal of Emerging and Selected Topics in Power Electronics, 2025-10. Verfasst von Prashant Kumar und 2 weiteren Autor:innen. Die Arbeit wurde bisher 7-mal zitiert (Crossref) und nennt 22 Literaturangaben.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

The voltage disturbances are compensated by a series-connected device called a dynamic voltage restorer (DVR) in a grid supply system. Three-phase DVR is operated with a proposed control based on zero-attracting LMS (ZA-LMS) for compensation of the voltage power quality (PQ) concerns. The ZA-LMS uses a variable step size for weight updating under dynamics. Second, the dc and ac link is associated with a severe voltage fluctuation, and it affects the performance of the DVR. To address this issue, an interval Type-2 fuzzy controller (IT2 FC) is developed and compared with a classical Type-1 fuzzy logic controller (T1 FLC). An osprey inspired optimizer (ISO) is utilized to achieve the optimum values of variables for T1 FLC and IT2 FC to accelerate the system response, save time, and achieve more accurate results. The parameters of antecedent and consequent are optimized by the ISO method, and observed that under a transitory scenario IT2 FC outperforms the T1 FLC with an improved response of settle time (Ts3), overshoot (Os3), and undershoot (Us3) of 0.121 s, 2.2%, and 5.6%, respectively. This shows that the IT2 FC yields potential results compared to conventional T1FC controllers under a dynamic environment. For validating the developed control schemes, simulation and experimentation results are demonstrated to show the efficacy of ZA-LMS integrated with IT2 FC under different grid conditions.

Zitieren

APA

Kumar, P., Arya, S. R., & Ray, P. (2025). Dynamic Voltage Restorer With Integration of Least Mean Square and Optimal Type-2 Fuzzy. IEEE Journal of Emerging and Selected Topics in Power Electronics, 13(5), 6253-6262. https://doi.org/10.1109/jestpe.2025.3572004

Vancouver

Kumar P, Arya SR, Ray P. Dynamic Voltage Restorer With Integration of Least Mean Square and Optimal Type-2 Fuzzy. IEEE Journal of Emerging and Selected Topics in Power Electronics. 2025;13(5):6253-6262. doi:10.1109/jestpe.2025.3572004

BibTeX
@article{Kumar2025,
  author = {Kumar, Prashant and Arya, Sabha Raj and Ray, Papia},
  title = {Dynamic Voltage Restorer With Integration of Least Mean Square and Optimal Type-2 Fuzzy},
  journal = {IEEE Journal of Emerging and Selected Topics in Power Electronics},
  year = {2025},
  volume = {13},
  number = {5},
  pages = {6253--6262},
  doi = {10.1109/jestpe.2025.3572004}
}