Wide Area Backup Protection Based on the Generalized Alpha Plane of Complex Powers
IEEE Access · 2026 · 14 · 168229-168242
DOI: 10.1109/access.2026.3747963 ↗Kurz gefasst
Fachartikel in der Zeitschrift IEEE Access, 2026. Verfasst von Vitor P. C. Romanini und 2 weiteren Autor:innen. Die Arbeit nennt 21 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: National Council for Scientific and Technological Development - CNPq, Brazil, Coordination for the Improvement of Higher Education Personnel - CAPES.
Abstract (Originalsprache)
This paper presents a wide-area backup protection algorithm based on the complex power differential principle, formulated in the Generalized Alpha Plane (GAP). In highly interconnected power systems, conventional backup protection schemes, particularly those based on distance protection functions, may face significant limitations due to the infeed effect, which reduces the effective reach of Zone 2 protection and increases the risk of undetected faults and cascading outages. To overcome these limitations, we propose a solution based on WAMPAC network infrastructure, using synchronized positive sequence phasors provided by Phasor Measurement Units (PMUs). The proposed method extends the Generalized Alpha Plane formulation from the current domain to the complex power domain. By applying synchrophasor measurements to a complex power differential formulation, the proposed approach eliminates dependence on local apparent impedance measurements. It enables protection decisions based on the protected area’s energy balance, overcoming limitations associated with the infeed effect. The effectiveness of the proposed approach was evaluated through studies conducted in two complementary simulation environments. The first employed ATP/EMTP to assess the algorithm robustness, sensitivity, and selectivity under different fault conditions. The second employed the ORGANON platform, which utilizes the actual network model maintained by the Brazilian National System Operator (ONS, the Portuguese acronym for Operador Nacional do Sistema Elétrico), enabling large scale dynamic assessments under realistic operating conditions through the reproduction of critical historical events associated with angular instability and voltage collapse in the Brazilian Interconnected Power System (BIPS). The results demonstrate that the proposed algorithm exhibits high robustness, maintaining reliable performance even under adverse conditions, and provides broader operational coverage than conventional approaches, thereby enhancing the security of complex transmission networks.
Förderung
- National Council for Scientific and Technological Development - CNPq, Brazil
- Coordination for the Improvement of Higher Education Personnel - CAPES
Zitieren
APA
Romanini, V. P. C., Silva, K. M., & Ribeiro, E. P. A. (2026). Wide Area Backup Protection Based on the Generalized Alpha Plane of Complex Powers. IEEE Access, 14, 168229-168242. https://doi.org/10.1109/access.2026.3747963
Vancouver
Romanini VPC, Silva KM, Ribeiro EPA. Wide Area Backup Protection Based on the Generalized Alpha Plane of Complex Powers. IEEE Access. 2026;14:168229-168242. doi:10.1109/access.2026.3747963
BibTeX
@article{Romanini2026,
author = {Romanini, Vitor P. C. and Silva, Kleber M. and Ribeiro, Eduardo Passos A.},
title = {Wide Area Backup Protection Based on the Generalized Alpha Plane of Complex Powers},
journal = {IEEE Access},
year = {2026},
volume = {14},
pages = {168229--168242},
doi = {10.1109/access.2026.3747963}
}
EUVIMED