EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

FEM-Based Quantification of Eddy-Current Losses for MV Cables in Trefoil Formation With Non-Magnetic Screens

Marko Šućurović, Dardan Klimenta, Nikolay Hinov, Dragan Tasić, Mladen Banjanin, Darius Andriukaitis

IEEE Access · 2026 · 14 · 47241-47258

DOI: 10.1109/access.2026.3678088 ↗

Kurz gefasst

Fachartikel in der Zeitschrift IEEE Access, 2026. Verfasst von Marko Šućurović und 5 weiteren Autor:innen. Die Arbeit wurde bisher 1-mal zitiert (Crossref) und nennt 45 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Circulating- and eddy-current losses occur in non-magnetic screens and armors of three medium-voltage (MV) single-core cables installed in trefoil formation, where they are bonded and earthed at both ends. According to IEC 60287-1-1, eddy-current losses in non-magnetic screens and armors should be neglected, whereas the technical brochure CIGRÉ TB 880 recommends that these losses should always be taken into account. For the considered screen bonding design, a reliable quantitative separation of circulating- and eddy-current losses is therefore essential. Such a separation cannot be performed accurately while simultaneously using experimental methods alone, but it can be achieved through a combination of analytical modeling and finite element method (FEM)-based electro–magneto–thermal simulations. This paper proposes and applies a new hybrid FEM-based procedure for the quantitative determination of circulating- and eddy-current losses in MV cables. The method is applied to Cu/XLPE/CTS/PVC/AWA/PVC 1/C 19/33 kV (BS 6622) cables with twelve different conductor cross-sections. The accuracy of the proposed procedure is verified by comparisons with IEC-based analytical calculations that account for eddy-current losses in accordance with the technical brochures CIGRÉ TB 272 and CIGRÉ TB 880. The FEM-based electro–magneto–thermal models are calibrated and validated using experimental data already published for PL $1\times 300$ RM 6/10 kV cables. The developed calibration strategy represents another novelty. The results demonstrated that, for the BS 6622 cables with conductor cross-sections ranging from 70 to 1000 mm2, the screen and armor eddy-current loss factors lie within the ranges 0.00094–0.03625 and 0.00719–0.1951, respectively. The deviations between the FEM- and IEC-based eddy-current loss factors range from −6.398% to 5.302%, demonstrating a very good agreement.

Zitieren

APA

Šućurović, M., Klimenta, D., Hinov, N., Tasić, D., Banjanin, M., & Andriukaitis, D. (2026). FEM-Based Quantification of Eddy-Current Losses for MV Cables in Trefoil Formation With Non-Magnetic Screens. IEEE Access, 14, 47241-47258. https://doi.org/10.1109/access.2026.3678088

Vancouver

Šućurović M, Klimenta D, Hinov N, Tasić D, Banjanin M, Andriukaitis D. FEM-Based Quantification of Eddy-Current Losses for MV Cables in Trefoil Formation With Non-Magnetic Screens. IEEE Access. 2026;14:47241-47258. doi:10.1109/access.2026.3678088

BibTeX
@article{uurovi2026,
  author = {Šućurović, Marko and Klimenta, Dardan and Hinov, Nikolay and Tasić, Dragan and Banjanin, Mladen and Andriukaitis, Darius},
  title = {FEM-Based Quantification of Eddy-Current Losses for MV Cables in Trefoil Formation With Non-Magnetic Screens},
  journal = {IEEE Access},
  year = {2026},
  volume = {14},
  pages = {47241--47258},
  doi = {10.1109/access.2026.3678088}
}