Automated Validation and Repair Framework for Converting Operational Distribution System Into Digital-Twin-Ready Simulation Models

Hasan Iqbal, Jawad Mohammed, Arif Sarwat

IEEE Access · 2026 · 14 · 47012-47031

DOI: 10.1109/access.2026.3677576 ↗

Kurz gefasst

Fachartikel in der Zeitschrift IEEE Access, 2026. Verfasst von Hasan Iqbal und 2 weiteren Autor:innen. Die Arbeit wurde bisher 2-mal zitiert (Crossref) und nennt 29 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Operational distribution networks maintained in ADMS and SCADA platforms are not directly usable in planning-grade simulation tools such as OpenDSS due to inconsistent schema definitions, incomplete asset attributes, electrically isolated network islands, invalid control references, and missing protection dependencies. These issues prevent repeatable feeder studies and hinder the creation of reliable baseline models required for digital-twin-enabled planning workflows. This paper presents an automated ingestion, validation, and repair framework that converts operational distribution exports into electrically consistent, simulator-ready feeder models. The framework (i) parses multi-table utility exports into a typed intermediate representation with unit and schema normalization, (ii) enforces a single energized connected topology using graph-based traversal from the source bus, (iii) repairs invalid regulator and capacitor monitoring references through topology-aware upstream tracing, and (iv) ensures protection instantiation by injecting a library of standard time-current characteristic curves prior to device generation. Each model build is versioned and evaluated using a repeatable verification protocol including compile-time integrity checks, topology metrics, and baseline power-flow validation. Case studies on anonymized real utility feeders demonstrate consistent compilation, elimination of electrically isolated islands, stable power-flow convergence, and valid control and protection instantiation without manual intervention. A yearlong, no-DER time-series validation confirms numerical stability and physically consistent voltage, energy, and loss trends under time-varying loading, while ablation studies show that each repair module is necessary to avoid characteristic model failure modes. The proposed framework establishes a scalable method for generating digital-twin-ready baseline feeder models from operational utility exports, enabling reliable downstream applications such as DER hosting-capacity analysis, planning studies, and long-horizon distribution system simulations.

Zitieren

APA

Iqbal, H., Mohammed, J., & Sarwat, A. (2026). Automated Validation and Repair Framework for Converting Operational Distribution System Into Digital-Twin-Ready Simulation Models. IEEE Access, 14, 47012-47031. https://doi.org/10.1109/access.2026.3677576

Vancouver

Iqbal H, Mohammed J, Sarwat A. Automated Validation and Repair Framework for Converting Operational Distribution System Into Digital-Twin-Ready Simulation Models. IEEE Access. 2026;14:47012-47031. doi:10.1109/access.2026.3677576