Research on the Influence of Ferromagnetic Resonance on the Temperature Rise Characteristics and Insulation Performance of Electromagnetic Voltage Transformers
IEEE Access · 2026 · 14 · 47127-47135
DOI: 10.1109/access.2026.3674101 ↗Kurz gefasst
Fachartikel in der Zeitschrift IEEE Access, 2026. Verfasst von Bai Lu und 6 weiteren Autor:innen. Die Arbeit nennt 23 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Science and Technology Project of State Grid Shanxi Electric Power Company.
Abstract (Originalsprache)
Electromagnetic potential transformers (PTs) in ungrounded distribution networks are prone to ferromagnetic resonance, causing overvoltage and overheating, which lead to insulation degradation and equipment failure. To reveal the internal failure mechanism, this study investigates the synergistic effects of ferroresonance on the temperature rise and insulation performance of PTs. Using a JDZ-10Q type PT, we obtained its nonlinear excitation characteristic curve experimentally. A transient ferroresonance model and a three-dimensional multi-physics coupling model were established to analyze the coupled electrical-thermal field distribution under resonance conditions. A partial discharge test platform was built to study the effects of different resonance types (high-frequency, fundamental frequency, low-frequency) and temperatures on the discharge behavior of interlayer insulation. Simulation and experimental results show that under ferroresonance, the primary voltage of the PT can exceed three times the rated value, the excitation current increases by several hundred times, and the maximum winding temperature rise reaches 176 °C, far exceeding the thermal endurance limit of the epoxy resin insulation. Partial discharge increases exponentially when the temperature exceeds 60 °C, with high-frequency resonance prone to dense discharges, and fundamental and low frequency resonances showing significantly increased discharge magnitude under high temperatures. The study reveals the synergistic mechanism of ferroresonance-induced PT insulation failure from the perspective of “electrical-thermal-insulation” multi-physics coupling, providing a theoretical basis for PT condition monitoring and resonance suppression.
Förderung
- Science and Technology Project of State Grid Shanxi Electric Power Company
Zitieren
APA
Lu, B., Dongdong, Y., Yu, Z., Shuqi, H., Chu, P., Wei, W., & Yutong, C. (2026). Research on the Influence of Ferromagnetic Resonance on the Temperature Rise Characteristics and Insulation Performance of Electromagnetic Voltage Transformers. IEEE Access, 14, 47127-47135. https://doi.org/10.1109/access.2026.3674101
Vancouver
Lu B, Dongdong Y, Yu Z, Shuqi H, Chu P, Wei W, et al. Research on the Influence of Ferromagnetic Resonance on the Temperature Rise Characteristics and Insulation Performance of Electromagnetic Voltage Transformers. IEEE Access. 2026;14:47127-47135. doi:10.1109/access.2026.3674101
BibTeX
@article{Lu2026,
author = {Lu, Bai and Dongdong, Yang and Yu, Zhang and Shuqi, Huang and Chu, Pei and Wei, Wang and Yutong, Chen},
title = {Research on the Influence of Ferromagnetic Resonance on the Temperature Rise Characteristics and Insulation Performance of Electromagnetic Voltage Transformers},
journal = {IEEE Access},
year = {2026},
volume = {14},
pages = {47127--47135},
doi = {10.1109/access.2026.3674101}
}
EUVIMED