A systematic analysis of data center water use, methodological divergence, and policy implications

Julia A. Davis, Landon T. Marston, Majid Shafiee-Jood

Environmental Research Communications · 30.10.2026

DOI: 10.1088/2515-7620/aebc1a ↗

Kurz gefasst

Fachartikel in der Zeitschrift Environmental Research Communications, online erschienen am 30.10.2026. Verfasst von Julia A. Davis und 2 weiteren Autor:innen. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: University of Virginia Environmental Institute, The Joyce Foundation, ARCS Foundation Metropolitan Washington Chapter.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Data center water use is an increasingly important yet poorly understood component of the environmental impacts of digital infrastructure. Reported estimates of data center water use vary by several orders of magnitude, creating interpretive challenges for policymakers, utilities, and the public. This study examines how methodological choices are associated with divergence across published estimates and evaluates implications for governance and reporting. We compile and analyze 100 estimates from 33 sources, including academic studies, government reports, corporate disclosures, and industry analyses, and classify each estimate across seven analytical dimensions spanning system boundary, water metric, operational assumptions, and temporal basis. Results show that divergence is structured rather than arbitrary. Within the same sources, estimates of indirect electricity-related water use (Scope 2) are approximately 2-12× larger than direct on-site use (Scope 1). Measurement choices, particularly the distinction between consumption and withdrawal, can produce differences ranging from modest to extreme, while cooling technology assumptions and facility composition introduce additional variability even in normalized metrics. Growth scenario assumptions further widen divergence between historical and projected values. These findings demonstrate that aggregated and modeled estimates of data center water use are not directly comparable without accounting for their methodological choices. We propose a minimum reporting standard of nine disclosure elements: system boundary, water metric, electricity attribution, cooling technology, operational efficiency definition, spatial scale, temporal resolution, growth scenario basis, and data provenance. We recommend consistent disclosure of these elements so that estimates can be matched to the decisions they can inform, such as benchmarking, utility planning, and permitting.

Förderung

  • University of Virginia Environmental Institute
  • The Joyce Foundation
  • ARCS Foundation Metropolitan Washington Chapter
  • Office of Postsecondary Education

Zitieren

APA

Davis, J. A., Marston, L. T., & Shafiee-Jood, M. (2026). A systematic analysis of data center water use, methodological divergence, and policy implications. Environmental Research Communications. https://doi.org/10.1088/2515-7620/aebc1a

Vancouver

Davis JA, Marston LT, Shafiee-Jood M. A systematic analysis of data center water use, methodological divergence, and policy implications. Environmental Research Communications. 2026. doi:10.1088/2515-7620/aebc1a

BibTeX
@article{Davis2026,
  author = {Davis, Julia A. and Marston, Landon T. and Shafiee-Jood, Majid},
  title = {A systematic analysis of data center water use, methodological divergence, and policy implications},
  journal = {Environmental Research Communications},
  year = {2026},
  doi = {10.1088/2515-7620/aebc1a}
}
Kostenlos starten →