EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

Operational challenges of positive pressure systems for radiation protection in medical facilities

Chihiro Matsumoto iD, Shota Tanabe, Chika Yamamoto iD, Tianchen Zhao, Toyoaki Sawano iD, Saori Nonaka, Hideyuki Kato, Fumie Yamaguchi iD, Shogo Takahara iD, Tomoaki Tanaka iD, Masaharu Tsubokura iD

Journal of Radiological Protection · 01.09.2026 · 46 (3) · 032501

DOI: 10.1088/1361-6498/ae80d3 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Journal of Radiological Protection, online erschienen am 16.07.2026. Verfasst von Chihiro Matsumoto und 10 weiteren Autor:innen. Beteiligte Einrichtung: Department of Radiation Health Management, Fukushima Medical University School of Medicine, Fukushima, Japan. Hauptthemen laut MEDLINE: Radiation Protection, Disaster Planning, Health Facilities, Radioactive Hazard Release. Die Arbeit nennt 25 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: JSPS KAKENHI, the Japan Science and Technology Agency, the Program of the Network-type Joint Usage/Research Center for Radiation Disaster Medical Science.

AbstractSchlagwörterBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

During nuclear disasters, shelter-in-place (SIP) is often a safer alternative to evacuation for patients in medical facilities who may be particularly vulnerable. In Japan, medical institutions located near nuclear facilities have been equipped with positive-pressure systems (PPS), designed specifically for radiation protection. However, operational protocols to execute and manage SIP and PPS remain poorly defined. This study aimed to investigate the challenges in implementing SIP at the time of nuclear catastrophe while maintaining essential clinical functions. A case study was conducted at the Matsue Red Cross Hospital, located within an urgent protective action planning zone. Data were gathered through participation in the hospital’s nuclear disaster countermeasures committee and through analysis of meeting minutes, facility documents, and technical specifications. The findings revealed a fundamental conflict between the technical requirements of PPS and the continuity of clinical services. Four critical sub-challenges were identified: (1) the unavoidable presence of certain staff and patients in non-protected zones within the hospital; (2) the potential inability to maintain sufficient positive pressure in protected zones during active clinical service; (3) the difficulty in regulating indoor temperature and humidity as a consequence of PPS operation; and (4) the increased risk of external radiation exposure in the vicinity of PPS units when outdoor ambient dose rates are elevated. For facilities that already have PPS installed, further investigations into PPS operations and the development of countermeasures are necessary. Furthermore, when installing PPS in the future, it is desirable for the government, hospitals, and installation companies to thoroughly discuss operations and design systems to minimise the impact on hospital functions.

Schlagwörter

MeSH-Schlagwörter (MEDLINE)

Radiation ProtectionDisaster PlanningHealth FacilitiesRadioactive Hazard ReleaseJapanHumansPressure

Stichwörter der Autor:innen

disaster preventionnuclear disastershelter-in-place

Autor:innen und Institutionen

  • Department of Radiation Health Management, Fukushima Medical University School of Medicine, Fukushima, Japan.
  • Emergency Department, Matsue Red Cross Hospital, Shimane, Japan.
  • Department of Surgery, Jyoban Hospital of Tokiwa Foundation, Fukushima, Japan.
  • Research Center for Community Health, Minamisoma Municipal General Hospital, Fukushima, Japan.
  • Division of Radiological Disaster, Chiba University Research Institute of Disaster Medicine, Chiba, Japan.
  • Department of General Medicine, Taito Hospital, Tokyo, Japan.

ORCID-Profile: Chihiro Matsumoto, Chika Yamamoto, Toyoaki Sawano, Fumie Yamaguchi, Shogo Takahara, Tomoaki Tanaka, Masaharu Tsubokura

Förderung

  • JSPS KAKENHI
  • the Japan Science and Technology Agency
  • the Program of the Network-type Joint Usage/Research Center for Radiation Disaster Medical Science
  • the internal fund of the Minamisoma Municipal General Hospital (Minamisoma, Fukushima, Japan) and the Department of Radiation Health Management, Fukushima Medi…

Zitieren

APA

Matsumoto, C., Tanabe, S., Yamamoto, C., Zhao, T., Sawano, T., Nonaka, S., Kato, H., Yamaguchi, F., Takahara, S., Tanaka, T., & Tsubokura, M. (2026). Operational challenges of positive pressure systems for radiation protection in medical facilities. Journal of Radiological Protection, 46(3), 032501. https://doi.org/10.1088/1361-6498/ae80d3

Vancouver

Matsumoto C, Tanabe S, Yamamoto C, Zhao T, Sawano T, Nonaka S, et al. Operational challenges of positive pressure systems for radiation protection in medical facilities. Journal of Radiological Protection. 2026;46(3):032501. doi:10.1088/1361-6498/ae80d3

BibTeX
@article{Matsumoto2026,
  author = {Matsumoto, Chihiro and Tanabe, Shota and Yamamoto, Chika and Zhao, Tianchen and Sawano, Toyoaki and Nonaka, Saori and Kato, Hideyuki and Yamaguchi, Fumie and Takahara, Shogo and Tanaka, Tomoaki and Tsubokura, Masaharu},
  title = {Operational challenges of positive pressure systems for radiation protection in medical facilities},
  journal = {Journal of Radiological Protection},
  year = {2026},
  volume = {46},
  number = {3},
  pages = {032501},
  doi = {10.1088/1361-6498/ae80d3}
}
Kostenlos starten →